Heat Controller A-VMH18DC-1 Air Conditioner User Manual


 
42
Service Manual VMH SerieS Heat Controller, Inc.
Replace the temperature sensor
Replace outdoor main board
High temperature
protection of condenser
Evacuate the refrigerant, then use the
high pressure nitrogen or refrigerant to
blow out the pipes, vacuum and recharge
the refrigerant again
Clean the heat exchanger
Stop the unit
Check whether the
condenser temperature is
more than 149°F (65°C)
Check whether the
outdoor ambient temperature is
higher than 122°F (50°C)
Check whether the
heat exchanger is dirty
The refrigerant
circuit is blocked
No
No
Yes
Yes
Yes
Yes
Yes
No
9.3.2.10 High temperature protection of condenser (ODU P6)
When outdoor pipe temp. is mroe than 149°F (65°C), the unit will stop, and will run again when outdoor
pipe temp. is less than 126°F (52°C).
No
Check whether the
resistance of condenser
temp. sensor is correct
refer to the Appendix 1
No
No