Heat Controller A-MMH18FA-1 Air Conditioner User Manual


 
- 30 -
Wall Mounted Multi-Zone Split System Air Conditioner
Flaring Work and Connection of Piping
Outdoor
Align the center of the piping and sufficiently tighten the flare
nut by hand.
Finally, tighten the flare nut with torque wrench until the
wrench clicks.
• When tightening the flare nut with torque wrench, ensure
the direction for tightening follows the arrow on the wrench.
Outdoor unit
36 kBtu/h
Liquid side piping
Torque wrench
B-UNIT
A-UNIT
Gas side piping
Torque wrench
Liquid side piping
B-UNIT
C-UNIT
A-UNIT
Gas side piping
Outdoor unit
18/24 kBtu/h
Outside diameter Torque
mm inch kg
.
m lbf.in
Ø6.35 1/4 1.8 156.2
Ø9.52 3/8 4.2 364.5