- 7 -
Air conditioner Edition: 100070808
Note: Sequence of defrosting actions:
9(or 7)minutes
Compressor ON
OFF
Four-way valve ON
OFF
Outdoor fan ON
OFF
55s 55s
1min 1min
Freezing prevention function
Under refrigerating and dehumidifying state, the air conditioner will control the
outdoor fan as per the temperature Tp of the indoor coil pipe according to the
following conditions:
Zone of return deference
Compressor,outdoor fan OFF after 5 minutes Fan,compressor ON
0 7 Tp(℃
.
)
3 minutes stand-by time
When the compressor ceases due to the sensor OFF, unit On or OFF or fault, it
will maintain pause for 3 minutes.
Overload protection during heating running
Temperature protection of indoor coil pipe: Under heating state, the air
conditioner will control the running of the fan as per the temperature Tp of the
indoor coil pipe and according to the following conditions:
a.
a.
58℃≤Tp, outdoor fan ceases; Tp≤54℃, outdoor fan resumes; the time
from ceasing to resuming is about 45 seconds;
b.
b.
68℃≤Tp, outdoor fan of compressor ceases after 5 seconds; Tp≤47℃,
compressor resumes after 3 minutes.
Current protection (different models have different protection currents):
a. When 13.0A ≤current of compressor, outdoor fan cease; current of compressor
≤11.7A, outdoor fan resume;
Compensatory function of power failure
If the unit is suddenly off during running due to power failure, or closed for
maintenance or troubleshooting, it will restart to run after the power resumes with
the original condition before the unit is off
Note: Function setting: Pressing the SLEEP button on the remote control unit
for 10 times until hearing 4 sounds from the buzzer on the panel.
Memory content: Running mode, setting wind speed, setting