Haier HSU-12H03/K(F) Air Conditioner User Manual


 
Outdoor unit
1.Connection of pipes
2.Atta
ching Drain-Elbow
To bend a pipe, give the roundness as large as possible not to crush the pipe
Connecting the pipe of gas side first ma
kes working easier.
The max
vertical distance between the indoor unit and the outdoor unit is 5 m.
If the drain-elbow is used, please attach it as
figure. (Note: Only for heat pump unit.)
Half union
Flare
nut
Spanner
Torque wrench
4
Outdoor unit
Forced fastening without careful centering
may damage the threads and cause a
leakage of ga
s.
Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.
3.Purging Method:
Push the air out of the indoor unit and piping as followes:
Tighten the caps on the valves with specified torque.
Valve rod
Valve cap
7-9
20-25
Tighten torque N.m
When connecting pipe exceeds 5 meters, 20g refrigerant shall be added per
exceeding meter. Charge according to the following list.
Piping length
Additional amount
5m 7m
No need
40g
10m
100g
for 09k 12k
Max. Length: for 9k A=7m
Max.Elevation:B=5m
for 12k A=10m
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
B
A
C
Outdoor unit
Indoor unit
Oil trap
A
B
CAUTION
In case more than 5 metresoil trap
should be installed every 5~7m.
C
Pipe Diameter ( )
Liquid side 6.35mm(1/4")
Gas side 9.52mm(3/8")
Fastening torque
18N.m
40N.m
Gas side 12.7mm(1/2") 55N.m