Electrical Load
Information
The following charts provide infor-
mation for the electrician wiring the
grain dryer, and are a reference
guide for parts. It is recommended
that you contact your local power
company and have a representatives
survey the installation to see that
your wiring is compatible with their
system and that adequate power is
supplied to your unit. Remember
that the only thing connected to the
recommended service amps should
be your grain dryer. Standard elec-
trical safety should be used. (Refer
to the National Electrical Code
Standard Handbook by the National
Fire Protection Association). A
qualified electrician should make all
electrical wiring installations.
Dryer Fan
Size Voltage Horsepower
Full Load
Amps
Motor
Starter
Relay
Heater
Strips
Fuse
(Slow Blow) Breaker
220v1ph 10-12 48 75 F614B 80 80
208v3ph 10-12 35 40 C400B 60 60
36" 220v3ph 10-12 33 40 C366B 60 60
380v50hz 10-12 15 30 C180B 30 30
460v3ph 10-12 17 30 C198B 30 30
575v3ph 10-12 15 30 C180B 30 30
220v1ph 10-16 78 90 F914B 100 100
208v3ph 15 44 60 C460B 60 60
36" 220v3ph 15 39 60 C400B 60 60
380v50hz 15 27 30 F772B 60 60
460v3ph 15 20 30 C228B 30 30
575v3ph 15 16 30 C198B 30 30
220v1ph 10-16 78 90 F914B 100 100
208v3ph 15 44 60 C460B 60 60
42" 220v3ph 15 39 60 C400B 60 60
380v50hz 15 27 30 F772B 60 60
460v3ph 15 20 30 C228B 30 30
575v3ph 15 16 30 C198B 30 30
208v3ph 20 61 75 F772B 80 80
220v3ph 20 50 60 C500B 80 80
42" 380v50hz 20 32 40 C366B 60 60
460v3ph 20 25 30 C303B 40 40
575v3ph 20 20 30 C228B 40 40
208v3ph 30 80 90 F104C 150 150
220v3ph 30 74 75 F772B 150 150
42" 380v50hz 30 39 40 C440B 80 80
460v3ph 30 37 40 C400B 80 80
575v3ph 30 30 40 C330B 80 80
208v3ph 40 108 120 F118C 200 200
220v3ph 40 102 120 F118C 200 200
42" 380v50hz 40 47 60 C500B 100 100
460v3ph 40 51 60 C550B 100 100
575v3ph 40 40 60 C400B 100 100
ELECTRICAL POWER SUPPLY