Goodman Mfg GMVM96 Furnace User Manual


 
PRoDucT sPeciFicATions
PRoDucT sPeciFicATions
SS-GMVM96 www.goodmanmfg.com 5
gcVM96 D
iMensions
FOLDED FLANGES
UNFOLDED FLANGES
FOLDED FLANGES
UNFOLDED FLANGES
MiniMuM cleARAnces To coMbusTible MATeRiAls
      
Downow 0” 0” 3” NC 0” 1”
Horizontal 6” 0” 3” C 0” 6”
C = If placed on combusble oor, the oor MUST be wood ONLY.
NC = For installaon on non-combusble oors only. A combusble oor sub-base must be used for installaons on combusble ooring.

For servicing or cleaning, a 24” front clearance is required.
Unit connecons (electrical, ue and drain) may necessitate greater clearances than the minimum clearances listed above.
In all cases, accessibility clearance must take precedence over clearances from the enclosure where accessibility clearances are greater.
 D H A B C D E
GCVM960604CX 21" 28¾" 40¾" 21" 19½” 16⅛" 18" 19½”
GCVM960805DX 24½” 28¾" 40¾" 24½” 23" 20⅝" 21½” 23"
GCVM961005DX 24½” 28¾" 40¾" 24½” 23" 20⅝" 21½” 23"

Installer must supply one or two PVC pipes: one for combuson air (oponal) and one for the ue outlet (required). Vent pipe must be either 2” or
3” in diameter, depending upon furnace input, number of elbows, length of run, and installaon (1 or 2 pipes). The oponal Combuson Air Pipe is
dependent on installaon/code requirements and must be 2” or 3” diameter PVC.
Line voltage wiring can enter through the right or le side of the furnace. Low-voltage wiring can enter through the right or le side of furnace.
Conversion kits for high-altude natural gas operaon are available. Contact your Goodman distributor or dealer for details.
Installer must supply following gas line ngs, according to which entrance is used:
Le—Two 90º elbows, one close nipple, straight pipe
Right—Straight pipe to reach gas valve
For boom return: Failure to unfold anges may reduce airow by up to 18%. This could result in performance and noise issues.