ProduCt SPeCifiCAtionS
ProduCt SPeCifiCAtionS
SS-GARPF www.goodmanmfg.com 5
Airflow dAtA


 0.1" 0.2" 0.3" 0.4" 0.5"
ARPF182416*
High 1,155 1,090 1,025 950 895
Med. 940 890 860 815 755
Low 695 665 650 610 550
ARPF193116*
High 1,135 1,085 1,025 965 915
Med. 860 825 780 750 680
Low 600 570 545 500 465
ARPF303016*
High 1,385 1,315 1,240 1,155 1,065
Med. 1,340 1,290 1,230 1,140 1,050
Low 1,075 1,030 980 910 840
ARPF363616*
High 1,310 1,240 1,155 1,090 1,020
Med 1,270 1,210 1,140 1,075 980
Low 1,045 1,005 955 885 805
ARPF364216*
High 1,700 1,660 1,625 1,545 1,505
Med. 1,500 1,440 1,400 1,350 1,345
Low 1,370 1,300 1,250 1,230 1,220
ARPF374316*
High 2,065 2,000 1,925 1,860 1,780
Med. 1,685 1,635 1,550 1,470 1,410
Low 1,490 1,425 1,345 1,280 1,205
ARPF486016*
High 2,150 2,120 2,070 2,000 1,940
Med. 1,940 1,930 1,905 1,860 1,790
Low 1,610 1,600 1,590 1,575 1,550
ARPF496116*
High 2,150 2,105 2,040 1,970 1,880
Med. 1,960 1,935 1,895 1,825 1,750
Low 1,670 1,625 1,585 1,525 1,455
Note: Assumes dry coil with lter in place; SCFM correcon for wet coil = 4% (208V / 240V