2.4 REFRIGERATION CYCLE
2.4.1 CONDENSER
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the brace.
(Refer to section 2.2.1)
3. Remove the 7 screws which fasten the condenser.
4. After discharging the refrigerant completely into a
Freon
TM
Recovery System, unbraze the
interconnecting tube at the condenser
connections.
5. Remove the condenser.
6. Re-install the components by referring to the notes
– on pages 11-13. (See Fig. 15)
2.4.2 EVAPORATOR
1. Remove the cabinet. (Refer to section 2.1.2)
2. Discharge the refrigerant completely – into a
Freon
TM
Recovery System.
3. Remove the 2 screws which fasten the evaporator
at the left side and the right side.
4. Move the evaporator to the side carefully and then
unbraze the interconnecting tube at the evaporator
connectors.
5. Remove the evaporator.
6. Re-install the components by referring to the notes
– on pages 11-13. (See Fig. 16)
2.4.3 CAPILLARY TUBE
1. Remove the cabinet. (Refer to section 2.1.2)
2. After discharging the refrigerant completely – into
a Freon
TM
Recovery System, unbraze the
interconnecting tube at the capillary tube.
3. Remove the capillary tube.
4. Re-install the components by referring to the notes
– on page 11-13.
Figure 15
Figure 16
Discharge the refrigerant system using a Freon
TM
Recovery System.
Install a valve for the recovery, before venting
the Freon, remove the valve when finished.
CAUTION