Friedrich H)A12K34L Air Conditioner User Manual


 
8
ELECTRICAL REQUIREMENTS
Wire Size
Unit MUST
Sample Nameplate
120524
COOLINGEQUIPMENT
FOLLOWINGITEMS
OUTDOORGRILLE
INDOORGRILLE
SAMPLE
Electrical Rating Tables
41A51
21A02
01A03
All units must be hard wired with properly sized breaker. See nameplate for specific chassis electrical requirements.
Supply voltage
See Electrical Rating Table below for wire size. Use HACR type breakers to avoid nuisance trips. All field wiring must be done
in accordance with NEC and local codes.
ELECTRIC SHOCK HAZARD
WARNING
Turn off electric power before service or instal-
lation. All electrical connnections and wiring
MUST be installed by a qualified electrician and
conform to the National Electrical Code and all
local codes which have jurisdiction. Failure to
do so can result in personal injury and/or death.
Supply voltage to the unit should be a nominal 208/230 volts. It must be between 197 volts and 253 volts. Supply voltage to
the unit should be checked WITH THE UNIT IN OPERATION. Voltage readings outside the specified range can be expected
to cause operating problems. Their cause MUST be investigated and corrected.
“Use ONLY time delayed fused disconnect or HACR type circuit breaker as indicated on the unit’s rating plate (see
sample on this page). Proper current protection to the unit is the responsibility of the owner”.