Service Manual 26
Troubleshooting Guide
COMPLAINT CAUSE REMEDY
Fan motor noise. Fan If cracked, out of balance, or partially missing,
replace it.
Blower If cracked, out of balance, or partially missing,
replace it.
Loose set screw Tighten it.
Worn bearings If knocking sounds continue when running or
loose, replace the motor. If the motor hums or
noise appears to be internal while running,
replace motor.
Compressor will not run, Voltage Check voltage. See the limits on the preceding
fan motor runs. page. If not within limits, call an electrician.
Wiring Check the wire connections; if loose, repair or
replace the terminal. If the wires are discon-
nected, refer to wiring diagram for identification,
and replace the wires. Check the wire connections;
If not according to the wiring diagram, correct
the connections.
Thermistor Check the TEMP control. If not at the lowest
number, set TEMP control to this setting and
restart the unit.
Check the continuity of the thermistor. Replace
the thermistor if the circuit is open.
Rotary Check for continuity, refer to the wiring diagram
for terminal identification. Replace the switch if
the circuit is open.
Thermostat Check the position of knob. If not at the coldest
setting, advance the knob to this setting and
restart the unit.
Check the continuity of the thermostat. Replace
the thermostat if the circuit is open.
Capacitor (discharge Check the capacitor.
capacitor before Replace if not within ±10% of manufacturer’s
servicing.) rating, replace if shorted, open, or damaged.
Compressor Check the compressor for open circuit or
ground. If open or grounded, replace the
compressor.
Overload
Check the compressor overload if externally mounted.
Replace if open. (If the compressor temperature is
high, remove the overload, cool, and retest.)