First Alert SA340B Smoke Alarm User Manual


 
brkelectronics.com
ARCHITECTURAL AND ENGINEERING SPEC
TOP
VIEW
2.0”
INSTALLATION OF ALARM
The smoke alarm shall be a First Alert Model SA340B and shall provide at a minimum
the following features and functions:
1. A dual ionization sensing chamber.
2. The unit shall be capable of self restoring.
3. Powered by a sealed 10-year lithium powercell with a tamperproof design. The
tamperproof design shall not allow the powercell to be removed after installation. A
low power warning indicator shall cause the alarm to “chirp” when it reaches the
end of its service life and needs to be replaced. Upon end of life, the unit shall meet
UL requirements for disabling the alarm and the non-reinstallation of unit to
mounting bracket.
4. A solid state piezo horn rated at 85 dB at 10 feet.
5. A visual LED power-on indicator to confirm unit is receiving power or
is in alarm.
6. A full function test button. The test button should check all alarm
functions by stimulating the chamber to simulate a smoke condition,
causing the unit to alarm and also has a silence feature to silence unwanted
nuisance alarms.
7. The unit shall be capable of operating between 40°F (4°C) and
100°F (38°C) and relative humidity between 10% and 90%.
8. The unit shall contain mounting hardware and shall be listed for wall
or ceiling mounting.
9. The unit shall at a minimum meet the requirements of UL217, CSFM,
NFPA 72, NFPA 101, ICC.
Installation of this smoke alarm must conform to NFPA 72. Always check your local
building codes. Follow all instructions for placement as outlined in the user’s manual.
SHIPPING SPECS:
TECHNICAL SPECS
Individual Carton Dimensions 5.75 ”L x 2.00”W x 6.75”H
Weight 0.55 lbs.
Cube 0.05 ft3
UPC 0 29054 00066 8
Master Carton Dimensions 12.75”L x 6.00”W x 7.25”H
Master Pack 6
Weight 3.6 lbs.
Cube 0.32 ft3
I2 of 5 100 29054 00066 5
Pallet Information
Cases per Layer 24
Number of Layers 6
Cases per Pallet 144
Units per Pallet 864
Cube 46.8 ft3
Weight 786 lbs.
Alarm Dimensions: 5.6” dia x 2.0”H
Weight: 6.9 oz.
Operating Voltage: 9V (three 3V) Lithium Power Cells
Temperature Range: 40°F (4°C) to 100°F (38°C)
Humidity Range: 10% to 90% relative humidity (RH)
Audio Alarm: 85dB at 10 feet
Test/Silence: Electronically simulates smoke condition,
causing the unit to alarm
Manual: Press and hold test/silence button
Alarm Reset: Automatic when smoke clears
Smoke Sensor: Dual Ionization
Indicator Lights/Sounds:
DC Power: Intermittent Red Light
Alarm: Audio alarm, rapidly flashing red light
Listing: Listed to UL217 Standard
SIDE
VIEW
BACK
VIEW
CAT.
SA340B
©2009 BRK Brands, Inc. a Jarden Corporation
Company (NYSE: JAH)
3901 Liberty Street Road
Aurora, IL 60504-8122
All rights reserved
First Alert is a registered trademark of the First Alert Trust
BRK is a registered trademark of BRK Brands, Inc.
CM2910
THE PARTS OF THIS SMOKE ALARM
1. Mounting bracket
2. Mounting slots
3. 10-Year Lithium Powercell
4. De-activation Tab
(located under label)
5.6”
HOW TO ACTIVATE AND DE-ACTIVATE THIS ALARM
Inserting Powercell De-activating Alarm