ARCHITECTURAL AND ENGINEERING SPEC
INSTALLATION OF ALARM
The carbon monoxide alarm shall be a First Alert Model CO600 (no battery backup/no
display), a CO605 (battery backup/no display) or a CO615 (digital display/battery
backup) and shall provide at a minimum the following features and functions:
1. An electrochemical CO sensor.
2. The unit shall have a digital display with peak CO memory feature (CO615 only).
3. The unit shall have an "End of Life" signal. This signal should be capable of
temporarily being silenced for up to 2 days. After about 2 days, the signal will
resume. After about 2-3 weeks the signal cannot be silenced.
4. Powered by 120V AC, 60Hz. and a solid state piezo horn rated at 85dB at 10 ft.
Models CO605 and CO615 feature a 2 AA battery backup and line cord to allow for
multiple placement options.
5. The CO sensor is adjusted not to detect CO levels below 30 PPM and will not
alarm when exposed to constant levels of 30 PPM for 30 days. It will alarm
at the following levels: 400 PPM CO between 4 and 15 minutes, 150 PPM CO
between 10 and 50 minutes and 70 PPM CO between 60 and 240 minutes.
6. A red LED power-on indicator to confirm unit is receiving power or is in alarm.
7. A full function test button should check all alarm functions by simulating a CO
condition, causing the unit to alarm.
8. Two Silence features - Low Battery Silence (Excludes CO600): Silence low battery
chirp for up to 8 hours. Alarm Silence: Temporarily silence nuisance alarms.
9. The unit shall be capable of operating between 40°F (4°C) and
100°F (38°C) and relative humidity between 10% and 95%.
10. The unit shall at a minimum meet the requirements of UL2034, NFPA 720,
NFPA 101, ICC.
Installation of this alarm must conform to NFPA 720. Always check your local building
codes. Follow all instructions for placement as outlined in the user’s manual.
SHIPPING SPECS:
TECHNICAL SPECS
Individual Carton Dimensions 5.44 ”L x 2.38”W x 3.44”H (CO600B)
5.75 ”L x 3.00”W x 2.94”H (CO605B, CO615B)
Weight 0.34 lbs. (CO600B)
0.62 lbs. (CO605B)
0.63 lbs. (CO615B)
Cube 0.024 ft3 (CO600B)
0.029 ft3 (CO605B, CO615B)
UPC 0 29054 00073 6 (CO600B)
0 29054 00072 9 (CO605B)
0 29054 00192 4 (CO615B)
Master Carton Dimensions 7.4”L x 7.4”W x 6.1”H (CO600B)
9.13 ”L x 7.13”W x 6.31”H (CO605B, CO615B)
Master Pack 6
Weight 2.33 lbs. (CO600B)
3.68 lbs. (CO605B)
3.90 lbs. (CO615B)
Cube 0.193 ft3 (CO600B)
0.238 ft3 (CO605B, CO615B)
I2 of 5 600 29054 00073 8 (CO600B)
600 29054 00072 1 (CO605B)
600 29054 00192 6 (CO615B)
Pallet Information
Cases per Layer 30 (CO600B)
27 (CO605B, CO615B)
Number of Layers 6 (CO600B)
7 (CO605B, CO615B)
Cases per Pallet 180 (CO600B)
189 (CO605B, CO615B)
Units per Pallet 1,080 (CO600B)
1,134 (CO605B, CO615B)
Cube 34.8 ft3 (CO600B)
52.0 ft3 (CO605B, CO615B)
Weight 484 lbs. (CO600B)
760 lbs. (CO605B)
802 lbs, (CO615B)
©2010 BRK Brands, Inc. a Jarden Corporation
Company (NYSE: JAH)
3901 Liberty Street Road
Aurora, IL 60504-8122
All rights reserved
First Alert is a registered trademark of the First Alert Trust
BRK is a registered trademark of BRK Brands, Inc.
CM3082
THE PARTS OF THESE CO ALARMS
1. Open door here 5. (Behind Cover) Alarm Horn
2. Test/Silence button 6. Peak Level Button (CO615B only)
3. POWER/ALARM Light 7. Digital Display (CO615B only)
4. (Behind Door) AA Battery
Compartment (CO605/CO615B only)
Alarm Dimensions: 3.3”H x 4.8"L x 1.5"D (CO600B)
3.3”H x 4.8"L x 2.1"D (CO605B, CO615B)
Weight: 4.0 oz. (CO600B)
6.6 oz. (CO605B)
7.2 oz. (CO615B)
Operating Voltage: 120V AC 60 Hz
Two 1.5V AA Alkaline Battery Backup (CO605B, CO615B)
Temperature Range: 40°F (4°C) to 100°F (38°C)
Humidity Range: 10% to 95% relative humidity (RH)
Audio Alarm: 85dB at 10 feet
Test/Silence: Electronically simulates CO conditions, causing the unit to
alarm or temporarily silence the alarm
Alarm Reset: Automatic when CO clears
CO Sensor: Electrochemical
Indicator Lights/Sounds:
AC Power: Constant red light
DC Power: Intermittent red light
CO Alarm: Audio Alarm (4 beeps, pause, 4 beeps), rapidly
flashing red light
Digital Display: (CO615B only) Displays battery level, CO levels in parts per
million (PPM), Peak CO level
Listing: Listed to UL 2034 Standard
CAT.
CO600B/CO600B/CO615B
CO
CO600/CO605B CO615B
TOP VIEW SIDE VIEW BACK VIEW
4.8"
CO600B/CO605B
3.3"
3.3"
1.5"
2.8"
CO615B