3
T
he basic installation of this Smoke Alarm is similar whether you want to
i
nstall one Smoke Alarm, or interconnect more than one Smoke Alarm. If you
are interconnecting more than one Smoke Alarm, you MUST read “Special
Re
quirements For Interconnected Smoke Alarms” below before you begin
i
nstallation.
E
LECTRICAL SHOCK HAZARD.Turn off power to the area where you
w
ill install this unit at the circuit breaker or fuse box before beginning
installation. Failure to turn off the power before installation may result
i
n serious electrical shock, injury or death.
1
. Using wire nuts, connect the power connector to the household wiring.
Improper wiring of the power connector or the wiring leading to the
po
wer connector will cause damage to the Alarm and may lead to a
n
on-functioning Alarm.
2. Remove the mounting bracket from the base, and attach it to the
junction box.
3. Plug the power connector into the back of the Smoke Alarm.
4.
Position the base of the Smoke Alarm over the mounting bracket and
turn. The Alarm will remain secure over a wide rotation range to allow for
perfect alignment.When wall mounting, this will allow fine-tuning on the
positioning to compensate for misaligned wall studs and to keep the
wording level.The Alarm can be positioned over the bracket every 120°.
Rotate the Alarm until aligned properly.
5. Check all connections.
ELECTRICAL SHOCK HAZARD. Do not restore power until all Smoke
Al
arms are completely installed. Restoring power before installation is
complete may result in serious electrical shock, injury or death.
6. Make sure the Smoke Alarm is receiving AC power. Under normal
operation, the Green power indicator light will shine continuously.
7. If the Green power indicator light does not light,
TURN OFF POWER TO
T
H
E
J
U
NCTION BOX
a
nd r
e
che
ck a
ll connections. If all connections
are correct and the Green power indicator still does not light when you
restore the power, the unit should be replaced immediately.
8.
Single Station Alarms: Test each Smoke Alarm. Press and hold the
Test/Silence button until the unit alarms.
I
n
terconnected Alarms:
P
r
ess and hold the Test/Silence button until
the unit alarms. All interconnected Alarms should sound.The other
Alarms sou
nding only tests the interconnect signal between Alarms.
It does not test each Alarm’s operation. You must test each Alarm
i
ndividually to check if the Alarm is functioning properly.
If any unit in the series does not alarm, TURN OFF POWER and recheck
connections. If it does not alarm when you restore power, replace it
immediately.
S
PECIAL REQUIREMENTS FOR INTERCONNECTED SMOKE ALARMS
Failure to meet any of the above requirements could damage the
unit
s and cause them to malfunction, removing your protection.
AC and AC/DC Smoke Alarms can be interconnected. Under AC
power, all units will alarm when one senses smoke. When power is
i
nterrupted, only the AC/DC units in the series will continue to send
and recei
ve signals. AC powered Smoke Alarms will not operate.
I
nterconnected units can provide earlier warning of fire than stand-alone units,
especially if a fire starts in a remote area of the dwelling. If any unit in the series
se
nses smoke, all units will alarm.To determine which Smoke Alarm initiated an
a
larm, see table:
D
uring an Alarm:
O
n Initiating Alarm(s) Red LED(s) flashes (flash) rapidly
O
n All Other Alarms Red LED is Off
A
fter an Alarm (Latching):
O
n Initiating Alarm(s) Green LED(s) On for 2 seconds/Off for 2 seconds
O
n
All Other Alarms Green LED(s) On, Red LED(s) is Off
Compatible Interconnected Units
Interconnect units within a single family residence only. Otherwise all house-
holds will experience unwanted alarms when you test any unit in the series.
Interconnected units will only work if they are wired to compatible units and
all requirements are met. This unit is designed to be compatible with:
First Alert
®
Smoke Alarm Models SA4120, SA4121B, SA100B and BRK
Electronics
®
Smoke Alarm Models 9120, 9120B, SC6120B, SC9120B, 7010,
7010B,100S, 4120, 4120B, 4120SB, RM3 (Relay Module);
BRK Electronics
®
CO
Alarm Models CO5120BN, CO5120PDBN; BRK Electronics
®
Heat Alarm
Models HD6135F and HD6135FB.
Interconnected units must meet ALL of the following requirements:
• A maximum of 18 compatible units may be interconnected
(Maximum of 12 Smoke Alarms).
• The same fuse or circuit breaker must power all interconnected units.
• The total length of wire interconnecting the units should be less than
1000 feet (300 meters). The interconnect wire should be #18 gauge or
larger, rated at least 300V. If an interconnect wire is not already part of
your household wiring, you will need to install one. This type of wire is
commonly available at Hardware and Electrical Supply stores.
All wiring must conform to all local electrical codes and Article 760 of NFPA
70 (NEC). Refer to NFPA 72, NFPA 101, and/or your local building code for
further connection requirements.
STAND-ALONE ALARM ONLY:
Connect the white wire on the power connector to the neutral wire in
the junction box.
Connect the black wire on the power connector to the hot wire in the
j
unction box.
Tuck the orange wire inside the junction box. It is used for
interconnect only.
I
NTERCONNECTED UNITS ONLY:
S
trip off about 1/2” (12 mm) of the plastic coating on the orange wire
on the power connector.
Connect the white wire on the power connector to the neutral wire in
the junction box.
Connect the black wire on the power connector to the hot wire in the
junction box.
Connect the orange wire on the power connector to the interconnect
w
ire in the junction box. Repeat for each unit you are interconnecting.
N
ever connect the hot or neutral wires in the junction box to the orange
interconnect wire. Never cross hot and neutral wires between Alarms.
STAND-ALONE ALARM ONLY:
If you are only installing one Smoke Alarm, restore power to the
junction box.
INTERCONNECTED UNITS ONLY:
If you are interconnecting multiple Smoke Alarms, repeat steps
1-5 for each Smoke Alarm in the series.When you are finished,
restore power to the junction box.
6
7
8
4
3
1
5
4
3
1
5
2
A
B
}
}
A. Unswitched 120VAC
60 Hz source
B. To additional units; Maximum = 18 total
(Maximum 12 Smoke Alarms)
1
.
Smo
k
e
Alarm
2
.
Ce
i
l
i
ng or
Wall
3
.
P
o
w
e
r Con
nector
4
.
W
ir
e N
ut
5
.
J
u
nct
ion Bo
x
6
.
N
e
ut
r
a
l Wire (Wht)
7
.
I
n
t
e
r
connect Wire
(Orange)
8.Hot Wire (Blk)
FOLLOW THESE INSTALLATION STEPS
9
. For new construction, place supplied dust cover over Alarm to prevent
damage from dust and construction debris. When construction is com-
p
lete, remove cover.
Sm
oke will not be able to reach smoke sensor while cover is in place.
Cover must be removed!