Technical Specifications
Architectural Specifications
Shipping Specifications
This heat alarm should be installed in accordance with the NFPA’s Standard
72 (National Fire Protection Association, Batterymarch Park, Quincy, MA
02269) and any local codes that apply.
Use #18 AWG minimum solid or stranded wire. When interconnecting,
maximum wire length between any two is 1,500 feet for #18 AWG or
4,000 feet for #14 AWG (20 OHMS loop resistance).
DO NOT connect to any other type or model of heat or smoke alarm. Connect
heat alarms to a single AC branch circuit. If local codes do not permit, be
sure the neutral wire is common to both phases.
Installation of Heat Alarm
Individual Carton Dimensions 5-1/4" x 2-11/16"x 5-1/4"
Master Carton Quantity 10
Master Carton Dimensions 15-3/4" x 11-1/4"x 6"
Master Carton Weight 7.62 lbs.
150-1344E
Side View
Mounting Bracket
The heat alarm shall be a StyleLine design™ (2-1/8" high, 5"
diameter), powered by 120V AC, 60Hz source with a 9-volt battery
back-up. The alarm shall have a fixed temperature sensor set to
alarm at nominal 135°F (57°C). The alarm shall be rated at no
greater than .05W in standby. Operating temperature range shall
be between -10°F and 158°F; 10%-93% relative humidity; 100%
solid state circuits over an input range of 100-130V AC. A green
continuous power on indicator shall be a built-in light emitting
diode (LED) in the standby condition; a second red blinking LED
shall indicate that a sufficient 9-volt battery back-up is present;
when activated; the initiating alarm red LED shall flash while the
interconnected alarms remain extinguished. The test switch
shall activate the alarm function by electronically simulating
a temperature greater than 135°. The alarm shall mount to a
single gang box, 4" octagon junction box, or a square to round
drywall ring without screw removal. It shall have a Quick Connect
molded harness, pigtail wiring and separate mounting bracket.
It shall meet the requirements of U.L. Standard 539 and 217.
5"
2.125"
Item 5700
Model ADH
Product Weight 8.6 ounces
Operating Temperature -10°F to 158°F (-23°C to 70°C)
Interconnect Qty Up to 18 Firex devices maximum: 12 smoke alarm
items 5000, 4618 and 46182 (model FADC), 4518
(model ADC) and 4480 (model PAD). Up to 6 heat, car-
bon monoxide or smoke and carbon monoxide combi-
nation alarms maximum; Firex carbon monoxide alarm
item 6045 (model COQ8), Firex smoke and carbon
monoxide combination alarm item 7000 (model
FADCQ) or Firex heat alarm item 5700 (model ADH).
Electrical Rating 120V AC, 60HZ, 50mA max, 9 Volt Battery Back-up
Alarm Point 135°F (57°C) fixed temperature
triggers alarm
Horn Output 85 decibels at 10 feet
Listing U.L. 539 and 217
U.L. Recommended
Coverage 2500 square feet
U.L. Recommended
Spacing 50 feet
Maximum Distance
from Wall 25 feet
Item 5700
©2003 Invensys Climate Controls Americas
3505 Laird Road Unit #14
Mississauga Ontario L5L 5Y7 Canada
Cust. Service Telephone +1 800 668 6958
Cust. Service Facsimile +1 905 828 1265
Visit us on the web at
www.icca.invensys.com
Climate Controls Americas
191 E. North Avenue
Carol Stream Illinois 60188 USA
Cust. Service Telephone +1 800 951 5526
Cust. Service Facsimile +1 630 260 7299
For Technical Service
Telephone +1 800 445 8299
Facsimile +1 630 260 7299
mctechservices@invensys.com