The ULTRA-ZONE steam humidifier now comes equipped with a factory installed Z100, which acts as a
sacrificial metal. Put simply, the chemicals in the water will attack and cling to the . The chemicals
will not attack the other components inside the humidifier as long as the Is active.
This results in a dramatic decrease in chemical and scale build up on the stainless steel components
inside the tank. In particular, it means less scale build up on the heating element which is subject to
damage from excessive scaling and over heating. This also means that efficiency stays high and
preventive maintenance is and .
The is positioned on the baffle plate inside the tank and is easily removed and replaced.
Remember that the ’s job is to become the target of chemical attack, so it will be heavily covered
with scale and should be replaced annually for best results.
To remove the you must have already unplugged and shutdown your steam humidifier and
allowed it to cool. The water tank has been drained, the water supply, drain lines and electrical wiring
have been disconnected and the unit has been removed from the duct.
Using a phillips screwdriver, remove the two screws that hold the baffle plate to the tank. Lift the baffle
slightly back to clear the water probe and then straight up and out of the tank. You can then see the
round , or rather what is left of it after a single season. Notice the heavy scale build up on the
that would have been on your element, if the was not there. Use a rag or pliers to grasp the edges
of the and simply unscrew it from the baffle plate. Rinse off or wipe away any residual scale from
the baffle plate and install the new . Leave a slight gap between the bottom of the and the
baffle plate. Now re-insert the baffle plate into the tank and secure with the two screws that were
removed previously. It’s that simple.
The can also benefit the older model steam humidifiers. Simply lay the down into the baffle
plate in the same location as the factory installed model. DO NOT lay the down into the main
tank. It may come in contact with the heating element and damage it. The dimensions of the baffle
plate prevent the from falling down into the tank.
The Z100 is just the latest innovation in the ULTRA-ZONE Steam Humidifier line as we continue in our
pursuit of Excellence Without Compromise.
Z100
Z100
faster easier
Z100
Z100
Z100
Z100 Z100
Z100
Z100
Z100 Z100
Z100 Z100
Z100
Z100
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
P/N 090376A0131 REV. B COPYRIGHT © 2002-2006, EWC Controls Inc., All Rights Reserved
Field Controls Inc. 2630 Airport Road Kinston, NC 28504 PH: 252.522.3031 FAX: 252.522.0214
P/N 090376A0131 REV. C 10/2011 Copyright © 2011, Field Controls Inc., All Rights Reserved
The Field Controls Steam Humidifier now comes equipped with a factory installed Z100, which acts
as a sacrificial metal. Put simply, minerals in the water will attack and cling to the Z100. The
minerals will not attack the other components inside the humidifier as long as the Z100 is present
and active.
This results in a dramatic decrease in mineral and scale build up on the critical components inside
the tank. In particular, it means less scale build up on the heating element which is subject to
damage from excessive scaling and over heating. This also means that efficiency stays high and
preventive maintenance is faster and easier.
The Z100 is positioned on the baffle plate inside the tank and is easily removed and replaced.
Remember that the Z100ʼs job is to become the target of mineral attack, so it will be heavily
covered with scale and should be replaced annually for best results.
To remove the Z100 you must have already unplugged and shutdown your steam humidifier and
allowed it to cool. The water tank has been drained, the water supply, drain lines and electrical
wiring have been disconnected and the unit has been removed from the duct.
Refer to the blow up view on Page 11. Using a phillips screwdriver, remove the two screws that
hold the baffle plate to the tank. Lift the baffle slightly back to clear the water probe and then straight
up and out of the tank. You can then see the round Z100, or rather what is left of it after a single
season. Notice the heavy scale build up on the Z100 that would have been on your element, if the
Z100 was not there. Use a rag or pliers to grasp the edges of the Z100 and simply unscrew it from
the baffle plate. Rinse off or wipe away any residual scale from the baffle plate and install a new
Z100. Leave a slight gap between the bottom of the Z100 and the baffle plate. Now re-insert the
baffle plate into the tank and secure with the two screws that were removed previously. Itʼs that
simple.
The Z100 can also benefit the older model steam humidifiers. Simply lay the Z100 down into the
baffle plate in the same location as the factory installed model. DO NOT lay the Z100 down into the
main tank. It may come in contact with the heating element and damage it. The dimensions of the
baffle plate prevent the Z100 from falling down into the tank.
SUPPLEMENT TO THE ELECTRONIC STEAM
POWER HUMIDIFIERS MODEL #S2000 AND S2020