Fedders CH1048CBD1VF Heat Pump User Manual


 
CH10 High Efficiency Series
MODEL SPECIFICATIONS
OUTDOOR
UNIT
MODEL*
EVAPORATOR
COIL
RATINGS AT STANDARD CONDITIONS
COOLING DATA AT EXTENDED OUTDOOR AMBIENTS °F.M.B.T.U.H.
BTUH
SEER
CFM
80 85 90 95 100 105 110 115
COOLING PERFORMANCE DATA MATCHED SYSTEM
CH1018BBD
E3009A 17600 10 600
TOTAL 18 700 18 300 17 900 17 600 16 700 15 800 14 800 13 900
SENSIBLE 13 500 13 200 12 900 12 700 12 020 11 400 10 700 10 000
CH1024BBD
E3009A 22600 10 800
TOTAL 24 500 23 900 23 200 22 600 21 400 20 200 19 000 17 900
SENSIBLE 17 600 17 200 16 700 16 300 15 400 14 500 13 700 12 900
CH1030BBD
E3612A 28200 10 1000
TOTAL 29 800 29 300 28 700 28 200 26 600 25 000 23 500 21 900
SENSIBLE 21 500 21 100 20 700 20 300 19 100 18 000 16 900 15 800
CH1036BBD
E3618A 34000 10 1250
TOTAL 37 300 36 400 35 500 34 600 31 900 28 800 25 900 23 000
SENSIBLE 26 900 28 400 25 600 24 900 23 000 20 700 18 600 16 600
CH1042CBD
E6016A 39500 10 1350
TOTAL 42 400 41 800 41 100 39 500 38 900 37 300 35 800 34 200
SENSIBLE 30 600 30 100 29 600 28 400 28 000 26 900 25 800 24 600
CH1048CBD
E6026A 46000 10 1700
TOTAL 49 700 48 500 47 300 46 000 44 400 43 000 41 500 39 800
SENSIBLE 35 800 34 900 34 000 33 100 32 000 31 000 29 900 28 600
CH1060CBD
E6037A 55500 10 1850
TOTAL 59 200 57 900 56 700 55 500 54 000 52 600 51 100 49 700
SENSIBLE 42 600 41 700 40 800 40 000 38 900 37 900 36 800 35 800
*Basic model number only. See unit nomenclature on the last page for exact model number.
FOOTNOTES:
Amps at 104˚F OD temp. 80˚F DB / 67˚F WB indoor temp. Time delay type fuse for HACR Circuit Breaker. For indoor coils nomenclature see
indoor coil specification sheet. Air handler includes evaporator coil.
MODEL NUMBER
CH1018BBD1VF CH1024BBD1VF CH1030BDD1VF CH1036BBD1VF CH1036BBD3VF CH1036BBD4VF
PERFORMANCE DATA
NOMINAL COOLING BTU/H 17 600 22 600 28 200 34 000
NOMINAL HEATING BTU/H 17 600 22 000 27 000 34 400
SEER (COOLING) BTU/H-W 10.0 10.0 10.0 10.0
CFM 600 800 1000 1250
VOLTS/HZ/PHASE 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/3 460/60/3
VOLTAGE RANGE 197-253 197-253 197-253 197-253 187-253 415-508
OPERATING CURRENT AMPS 9.2 12.0 15.4 18.0 13.2 6.2
MIN. WIRE AMPACITY 11.3 14.7 18.0 22.4 16.5 15.0
MAX. HACR BREAKER 15 25 30 35 25 15
COMPRESSOR DATA
RLA 8.8 9.8 11.4 15.2 11.4 4.8
LRA 49 60 75 96 75 40
FAN DATA
DIAMETER 18 INCH / 3 BLADE 18 INCH / 3 BLADE 18 INCH / 3 BLADE 18 INCH / 4 BLADE
MOTOR TYPE PSC PSC PSC PSC
HP (W) / FLA 1/6 / 1.0 1/6 / 1.0 1/6 / 1.0 1/5 / 1.8 1/4 / 1.2
RPM 1075 1075 1075 1075
CFM 1800 1800 1800 2400
OUTDOOR COIL
TYPE ENHANCED ALUMINUM PLATE FIN / RIFLED COPPER TUBE
FACE AREA 9.8 9.8 9.8 12.0
O.D. / F.P.I.-ROWS 5/16 / 18-1 3/8 / 18-1 3/8 / 18-1 3/8 / 18-1
REFRIGERANT LINE CONNECTIONS (SERVICE VALVE PORT I.D.)
LIQUID 3/8 ID 3/8 ID 3/8 ID 3/8 ID
VAPOR 3/4 ID 3/4 ID 3/4 ID 3/4 ID
WEIGHTS
NET WEIGHT — lbs. 137 140 142 161
SHIPPING WEIGHT — lbs. 143 149 151 169