Faber SPECTRA NOVA Indoor Fireplace User Manual


 
L
M
F
I
C
B
A
J
E
D
G
K
H
Builders opening (mm) Feeling Silence Whisper Spectra Cadra Misty
Nova Nova
A Opening width* 960 960 780 780 680 710
B Opening height* 649 649 705 698 798 890
C Opening depth* 385 385 430 430 430 370
Shelf dimensions
(combustible)
D Min. height shelf from
top frame 350 350 350 350 350 350
E Depth shelf max. 150 150 150 150 150 150
Dimensions (mm)
F Box width 880 880 750 750 650 698
G Box depth 366 366 397 375 375 338
H Box height 636 636 714 715 815 879
I Frame width 1064 1064 815 794 694 740
J Frame height 678 678 720 703 803 905
K Frame thickness 47 20 16 30 30 144
L Position flue
(behind frame) 255 255 257 235 235 196
M Position flue (from the
back side box) 111 111 140 140 140 142
UK/IRL
7
UK/IRL
6
3.1 Builders opening and surround (continuing)
If the builders' opening is constructed out of non-combustible
composition board (Fibrelux) and you install the appliance without a
mantel then:
- Ventilate the space above the appliance (min. 1000 mm
2
).
- Always fit the DC convection set.
- The plaster of the outside has to be resistant to a high
temperature. Use therefore the plaster materials especially made for
this, to prevent discoloring (min. 100 °C temperature resistant).
If the appliance is to be fitted against a wall with combustible
cladding, the cladding must be removed from the area covered by the
surround.
The minimum height from the top surface of the fire to the underside
of any shelf made from wood or other combustible materials is as
follows:
- For a shelf up to 150 mm deep – Minimum height = 350 mm
(fig. 1).
- If the shelf depth is greater than 150 mm add 50 mm to the upper-
clearance height for every 25 mm increase in shelf depth.
- Side clearance = Minimum distance from the side of the fire frame
to combustible material = 150 mm.
fig. 1
table 1
*the points A until C applies a tolerance from:
– 0 mm and + 5 mm.