Everpure SSFM-100BC-SYS Water System User Manual


 
©2007 Pentair Filtration, Inc. 340019 AU07
NOTES
A potable water storage tank should be treated whenever it is
filled from a shore source, or whenever there is no measurable
bromine residual in the tank. A measurable bromine residual
will insure the water is safe to drink.
SPECIFICATIONS
Dimensions
14"W x 44"H x 20
1
4"D
Dry Weight
SSFM-100BC-SYS: 119 lbs. (54 kg)
SSFM-100CC-SYS: 133 lbs. (60.3 kg)
SSFM-100DC-SYS: 141 lbs. (64 kg)
ELECTRICAL REQUIREMENTS
The recirculating brominator feeder requires a 115 VAC power
supply capable of supplying 1.5 amperes of current.
MOUNTING
The recirculating brominator feeder should be bulkhead
mounted within reasonable proximity to the motor-pump and
the line starter. A minimum of 13 inches overhead clearance
is required above the feeder assembly for easy removal of the
disposable bromine cartridge. For convenience, the instruction
plate with operating procedure should be bulkhead mounted
adjacent to the recirculating bromine feeder.
PLUMBING TERMINATIONS
Male quick disconnect coupling valve fittings are provided to
mate with the installation kit hoses for interconnection to the
motor-pump and potable water tank serviced.
ORDERING INFORMATION
BROMINATOR
MODEL PART NO.
REPLACES
PART NO.
NO. OF TANKS
SERVICED
SSFM-100BC-SYS 169090 EV906404 2
SSFM-100CC-SYS 169092 EV906406 3
SSFM-100DC-SYS 169094 EV906406 4
INSTALLATION KITS
In addition to your recirculating brominator, a separately
ordered motor-pump, line starter and installation kit are
required to make up the system. The installation kit comes
complete with interconnecting hoses and fittings.
BROMINATOR
MODEL NO.
INSTALLATION KIT
PART NO.
REPLACES
PART NO.
SSFM-100BC-SYS 169085 EV906332
SSFM-100CC-SYS 169086 EV906333
SSFM-100DC-SYS 169087 EV906334
Pentair Filtration, Inc.
502 Indiana Avenue - P.O. Box 1047
Sheboygan, Wisconsin 53082-1047
Phone 866.873.7506 Fax 888.203.7361
International Phone 920.457.9435 International Fax 920.457.2417
www.everpure.com
ALLOW 13” MINIMUM
FROM TOP OF FEEDER
TO OVERHEAD FOR
REMOVAL OF
CARTRIGE.