England's Stove Works 60-SHUNG Fan User Manual


 
INSTALLATION INSTRUCTIONS
1. Minimum inlet gas supply pressure must be 5.5” w.c. for natural gas and 11” w.c. for
propane (LP) gas for the purpose of adjustment. Maximum gas supply pressure must
not exceed 10.5” w.c. with natural gas, or 14” w.c. with propane (LP) gas. Use the
correct gas type for your appliance — check the tag for gas type and do not convert
from one to the other. If you are using propane the tank must be located outdoors.
Warning: Connecting directly to an unregulated propane tank can cause an
explosion.
2. Make gas connection grate assembly with:
a) Black iron pipe with malleable iron fittings.
b) An AGA approved corrugated metal connector
(not to exceed two feet (2’) in length).
c) Copper pipe or tubing, if acceptable to the authority having
jurisdiction. Copper pipe must be tinned.
3. Turn on the gas supply and check for leaks. DO NOT USE AN OPEN FLAME. Use a
soap and water solution for this check.
4. For the correct log positioning refer to “SET ASSEMBLY” as described later in the
manual.
5. Installation and provisions for combustion and ventilation air must conform to local
codes or in their absence the National Fuel Gas Code – ANSI Z21.11.2-1993
dated 5/95.
6. Keep the operating area clear and free of combustible materials, gasoline and other
flammable liquids and vapors.
7. The appliance and its individual shut off valve must be disconnected from the gas
supply piping system during any pressure testing of the gas supply piping system at
least equal to or less than ½ psig (3.5 kPa).
8. A one-eighth inch (1/8”) N.P.T. plugged tapping, accessible for test gauge
connection must be provided immediately upstream of the gas supply connection to
the appliance.
9. Never install appliance in: bedroom or bathroom, high traffic areas, recreational
vehicles, windy or drafty areas, or where curtains, furniture, clothing or flammable
objects are less than forty-two inches (42”) from the front of the appliance.
Important: The copper heat sensor attached to the valve should be placed outside and
to the rear of the stove for a more accurate room temperature reading.
Visit our web site at www.englandsstoveworks.com for helpful information, frequently
asked questions, parts and accessory orders and more.
Technical Problems: (800) 245-6489 Parts orders ONLY: (800) 516-3636