LISTING AND CODE APPROVALS
THIS VENTED GAS FIREPLACE HEATER HAS BEEN TESTED FOR COMPLIANCE WITH THE ANSI
STANDARD Z21.88-2002 AND THE CANADIAN CSA 2.33-M02 STANDARDS. THIS UNIT IS LISTED
WITH INTERTEK TESTING SERVICES (WARNOCK HERSEY, INC.) OF MIDDLETON, WISCONSIN. ALL
COMPONENTS ARE AGA, CGA, UL OR CSA APPROVED.
THIS APPLIANCE MUST BE INSTALLED IN ACCORDANCE WITH LOCAL CODES, IF ANY; IF NOT,
FOLLOW ANSI Z223.1 (NFPA 54), CURRENT EDITION IN THE U.S. OR CAN1-B149, CURRENT EDITION
INSTALLATION CODE IN CANADA.
NOTE: SEE LABEL ON THE VALVE FOR GAS PRESSURE TESTING LOCATION.
Performance Summary Table
Characteristic LP Gas Natural Gas
Fuel requirement LP Gas Natural Gas
Input rating (0-610m) 33,200 BTU/HR 32,000 BTU/HR
Minimum input (0-610m) 18,600 BTU/HR 22,500 BTU/HR
Input rating (610 – 1370m) 30,200 BTU/HR 29,300 BTU/HR
Orifice size (0-610m) #51 DMS #33 DMS
Max. inlet pressure 13.5” W.C. (3.36 kPa) 10.5” W.C. (2.61 kPa)
Min. inlet pressure 11.0” W.C. (2.74 kPa) 4.5” W.C. (1.12 kPa)
Max. manifold pressure 10.0” W.C. (2.49 kPa) 3.5” W.C. (0.87 kPa)
Min. manifold pressure 3.7” W.C. (0.92 kPa) 0.9” W.C. (0.22 kPa)
Max. efficiency, with fan 81.7% 77.9%
Max. output (0-610m) 27,300 BTU/HR 25,400 BTU/HR
Gas consumption (std. cond.) 13.3 Cu. Ft/hr or 0.4 gal/hr. 32 Cu. Ft/hr
Fuel supply line ½ inch (13 mm) ½ inch (13mm)
Flue exit 4” Diameter (Top or Rear) 4” Diameter (Top or Rear)
Chimney spec. Type B-1 (4” Dia.) Type B-1 (4” Dia.)
Ignition Piezo electric & pilot Piezo electric & pilot
Actual weight 161 lbs. 161 lbs.
Shipping weight 185 lbs. 185 lbs.
SECTION I: FLUE SYSTEM FOR VENTED GAS FIREPLACE HEATER
A. Installation of a New System (See Installation Drawings at the end of this Manual)
This vented gas fireplace heater must be connected to four-inch (4”) diameter Type B-1 gas
pipe. This product is manufactured and certified to NFPA 54 and NFPA 211 “current edition”
standards. The minimum clearance of this pipe to combustible materials is one inch (1”). Never
use aluminum or galvanized steel pipe with this unit.
Single wall pipe may be used between the stove and ceiling or stove and wall; a minimum of
six inches (6”) clearance to combustible materials is required for this type of pipe. It is imperative
that the single wall pipe be terminated at the ceiling or wall, by connecting to a double wall B-1
Vent Pipe. Single wall pipe should never pass through a combustible wall or ceiling. Follow the
pipe manufacturer’s instructions for venting through a combustible area.
Installation requirements for single wall pipe or Type B-1 Vent Pipe are specified in the ANSI
Z223.1 or CAN1-B149 Standard “current edition.” These standards will also indicate proper
clearances to combustibles. Your stove dealer or qualified service person will be familiar with
these standards and can properly install the chimney system.
Connection of the pipe to the stove is accomplished by placing the pipe over the collar on the
top or rear of the unit; then secure the connection with a screw through the pipe.