EMI CAF Humidifier User Manual


 
ELECTRICAL SPECIFICATIONS AND PERFORMANCE DATA
NOTE: Due to EMI’s ongoing product development program, all designs and specications are subject to change without notice.
ELECTRICAL SPECIFICATIONS
STANDARD UNIT DATA SMALL MEDIUM LARGE
   
 A 0.4 0.6 0.9
 A 0.5 0.75 1.13
 A 15 15 15
WITH OPTIONAL ELECTRIC HEAT
1
SMALL MEDIUM LARGE
   
 KW 1.5 3.0 5.0
 A 6.52 13.1 21.7
 A 7 13.7 22.6
 A 8.8 17.1 28.3
 A 15 20 30
WITH OPTIONAL BOOST TRANSFORMER
2
SMALL MEDIUM LARGE
   
 A 0.8 1.2 1.8
 A 1.0 1.5 2.26
 A 15 15 15



CAF HOT WATER CASSETTE CAPACITIES
(Hot Water 180°F Inlet/160° F Outlet)
Model
AIR ON °F
DB/50% RH
TC
Btuh
Flow
GPM
P.D. FT.
H
2
0
08
50° 19,800 2.0 10.0
60° 17,100 1.7 8.4
70° 14,000 1.4 6.7
18/20
50° 46,060 4.7 10.9
60° 41,930 4.3 9.4
70° 37,770 3.8 8.1
33/36
50° 62,500 6.4 10.8
60° 56,940 5.8 9.2
70° 51,350 5.2 7.3
SOUND LEVELS (dbA)
Model
High
Speed
Med.
Speed
Low
Speed
08-12 47 45 40
18 43 41 39
20 47 43 41
33-36 48 47 45
CAF TECHNICAL DATA
CABINET DIMENSIONS SMALL MEDIUM LARGE
 10-3/4” 9-1/2” 11-1/2”
 22-1/2” 32-1/4” 44-1/2”
 22-1/2” 32-1/4” 32-1/4”
   
FASCIA DIMENSIONS SMALL MEDIUM LARGE
 2-1/4” 3” 3”
 25” 37” 49-1/4”
 25” 37” 37”
   
CONNECTIONS SMALL MEDIUM LARGE
 5/8” 7/8” 7/8”
 5/8” 7/8” 7/8”
 3/8” 3/8” 3/8”
 5” 5” 6”
 3” 3” 3”
 5/8” 5/8” 5/8”
 5/8” 5/8” 5/8”
FILTRATION SMALL MEDIUM LARGE
 WIRE FRAMED PERIFRAME
 1 2 3
 80% 80% 80%
CONDENSATE PUMP SMALL MEDIUM LARGE
 30” 30” 30”
 0.1 0.1 0.1

DISCHARGE AIR VOLUME
Model
High
Speed
CFM
Med.
Speed
CFM
Low
Speed
CFM
08-12 400 340 300
18 615 550 490
20 750 615 550
33 996 890 784
36 1123 996 890
CAF CHILLED WATER CASSETTE CAPACITIES
COOLING CAPACITY CHILLED WATER INLET/OUTLET °F
MODEL
AIR ON °F
DB/50% RH
40/50° F 45/55° F
TC Btuh SC Btuh FLOW GPM P.D. FT. H20 TC Btuh SC Btuh FLOW GPM P.D. FT. H20
72 5460 5460 1.2 6.7 4780 4440 1.1 5.4
08 75 6480 6140 1.4 9.0 5460 5460 1.2 6.4
80 9550 7170 2.1 17.0 7500 6480 1.7 11.7
72 7850 7510 1.7 4.3 6480 6140 1.4 2.7
12 75 10580 8190 2.3 6.7 8190 7510 1.8 4.0
80 14670 9550 3.3 12.0 12280 8530 2.7 8.7
72 13480 12520 2.7 3.7 10100 10100 2.0 2.2
18 75 17310 13850 3.5 5.8 11670 11640 2.3 3.0
80 23410 15870 4.7 9.0 17810 13780 3.6 6.0
72 15050 14570 3.0 4.6 11670 11630 2.3 3.0
20 75 19140 15930 3.8 6.4 13510 13470 2.7 3.7
80 26650 18390 5.3 11.1 19990 15970 4.0 6.8
72 26310 21260 5.3 8.5 17610 17570 3.5 5.3
33 75 32070 23500 6.4 13.0 23060 19790 4.6 7.4
80 41760 26920 8.4 19.2 33130 23300 6.6 14.2
72 28490 23300 5.7 10.3 19210 19170 3.8 6.0
36 75 34700 25690 6.9 15.1 24910 21700 5.0 8.1
80 45810 29480 9.2 21.0 35830 25450 7.2 15.7

Enviromaster International LLC
5780 Success Drive, Rome, NY 13440
www.enviromaster.com