Model Ei161RC Ionisation
System Wiring
Wiring for Interconnected Alarms with optional Remote System Control Switch & Manual Call Point
Ensure correct wiring of the alarms and switches as mixing Live and Neutral will blow / damage interconnected units.
Technical Specification
Sensor Ionisation
Sensitivity: Complies with BS 5446 Part 1:
2000
Source: Americium 241 (33kBq)
Button Test: Simulates the effect of smoke and
checks electronics and horn
Automatic Self-Test: Circuitry is tested every 40
seconds and unit beeps if fault is
detected
Supply Voltage: 230V AC, 50Hz
Battery back up: Rechargeable Lithium cells
Power-On Indicator: Continuous green LED
Alarm: Electronic Piezoelectric horn
Alarm Sound Output: 85dB(A) (minimum) at 3m
Alarm Status: Red LED flashes every second on
unit sensing fire
Normal Operating
Temperature Range: 0 to 40°C
Humidity Range: 15% to 95% Relative Humidity
Interconnect: Up to 12 of these units can be
interconnected:
- Ei161RC/164RC/166RC smoke or
heat alarms
- Ei261ENRC/261DENRC CO alarm
- Ei128RBU relay base
Use with optional control (see below)
Optional Controls: - Ei1529RC Control Switch
- MCP401RC Manual Call Point
Fixing: Easi-fit mounting base
Plastic material: UL94VO flame retardant
Dimensions: 145mm diameter x 40mm depth
Weight: 281g
Guarantee: 5 year (limited)
Approvals: Kitemarked to BS EN 14604:2005
(License no. KM07862) and CE
certified