Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.+353 61 471277 Fx.+353 61 471053
Email. eielectronics@eiltd.ie
Web: www.eielectronics.com
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice. Ei161RC DataSht RevB
Model Ei161RC Ionisation
System Wiring
Wiring for Interconnected Alarms with optional Remote System Control Switch & Manual Call Point
Ensure correct wiring of the alarms and switches as mixing Live and Neutral will blow / damage interconnected units.
Technical Specification
Sensor Ionisation
Sensitivity: Complies with BS 5446 Part 1:
2000
Source: Americium 241 (33kBq)
Button Test: Simulates the effect of smoke and
checks electronics and horn
Automatic Self-Test: Circuitry is tested every 40
seconds and unit beeps if fault is
detected
Supply Voltage: 230V AC, 50Hz
Battery back up: Rechargeable Lithium cells
Power-On Indicator: Continuous green LED
Alarm: Electronic Piezoelectric horn
Alarm Sound Output: 85dB(A) (minimum) at 3m
Alarm Status: Red LED flashes every second on
unit sensing fire
Normal Operating
Temperature Range: 0 to 40°C
Humidity Range: 15% to 95% Relative Humidity
Interconnect: Up to 12 of these units can be
interconnected:
- Ei161RC/164RC/166RC smoke or
heat alarms
- Ei261ENRC/261DENRC CO alarm
- Ei128RBU relay base
Use with optional control (see below)
Optional Controls: - Ei1529RC Control Switch
- MCP401RC Manual Call Point
Fixing: Easi-fit mounting base
Plastic material: UL94VO flame retardant
Dimensions: 145mm diameter x 40mm depth
Weight: 281g
Guarantee: 5 year (limited)
Approvals: Kitemarked to BS EN 14604:2005
(License no. KM07862) and CE
certified
Specifications are subject to change