Drolet Hunter Wood Stove Stove User Manual


 
Couplings:
Once the wood stove is in place and the minimum clearances are respected, it must be
coupled to the chimney with a connector (commonly called “stove pipe”). Verify the
clearance between your stove pipe and the surrounding combustible material. If the
standard minimum 18 inch (457 mm) clearance cannot be obtained, you may use an
insulated stove pipe or a thermal protection shield. Read and respect the pipe
manufacturer's instructions before installation.
Your smoke evacuation system (should be assembled in such a way that the male sections
of the pipes face down. Attach each of the sections to one another with three equidistant
metal screws. The pipes must be short and straight. All sections installed horizontally
must slope at least 1/4 inch per foot, with the lower section toward the stove.
Installation of a "barometric draft stabilizer" (fireplace register) on your smoke exhaust
system is prohibited. Furthermore, installation of a draft damper is recommended.
Page 4 of 8