11 Device Information
1 Type and order code
LI 11MER
2Design
2.1 Model Reversible
2.2 Degree of protection according to EN 60 529 IP 21
2.3 Installation location Indoors
3 Performance data
3.1 Operating temperature limits:
Heating water flow/return flow °C / °C Up to 58 / above 18
Cooling, flow °C +7 to +20
Air (heating) °C -25 to +35
Air (cooling) °C +15 to +40
3.2 Temperature spread of heating water
at A7 / W35 K
9.6 5.0
3.3 Heat output / COP at A-7 / W35
1
kW / ---
1. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, other parameters, such as, in particular, the defrosting
capacity, the bivalence point and regulation, should also be taken into consideration. The specified values, e.g. A2 / W55, have the following meaning: External temperature 2 °C
and heating water flow temperature 55 °C.
7.5 / 2.8 7.0 / 2.7
at A-7 / W45
1
kW / ---
6.8 / 2.3
at A2 / W35
1
kW / ---
8.9 / 3.4 8.8 / 3.3
at A7 / W35
1
kW / ---
11.1 / 4.2 11.1 / 4.0
at A7 / W45
1
kW / ---
9.4 / 3.5
at A10 / W35
1
kW / ---
12.1 / 4.6 12.0 / 4.4
3.4 Temperature spread of cooling water
at A35 / W7 K
6.5 5.0
3.5 Cooling capacity / COP at A27 / W7 kW / --- 8.8 / 2.8 8.8 / 2.8
at A27 / W18 kW / --- 10.9 / 3.3 10.8 / 3.2
at A35 / W7 kW / --- 7.6 / 2.1 9.5 / 2.5
at A35 / W18 kW / --- 9.5 / 2.5 9.5 / 2.5
3.6 Sound power level device / outdoors dB(A) 55 / 61
3.7 Sound pressure level at a distance of 1 m (indoors) dB(A) 50
3.8 Heating water flow with an internal pressure differential of m³/h / Pa 1.0 / 3000 1.9 / 10900
3.9 Cooling water flow with an internal pressure differential ofm³/h / Pa 1.0 / 3000 1.3 / 5900
3.10 Air flow rate with an external static pressure differential of m³/h / Pa 4200 / 0
m³/h / Pa 2500 / 25
3.11 Refrigerant; total filling weight Type / kg R404A / 3.6
4 Dimensions, connections and weights
4.1 Device dimensions H x W x L cm 136 x 75 x 88
4.2 Device connections to heating system Inch G 1 1/4'' external
4.3 Air duct inlet and outlet (min. internal dimensions) L x W cm 50 x 50
4.4 Weight of the transportable unit(s) incl. packing kg 205
5 Electrical Connection
5.1 Nominal voltage; fuse protection V / A 230 / 25
5.2 Nominal power consumption
1
A2 W35 kW
2.61 2.67
5.3 Starting current with soft starter A 38
5.4 Nominal current A2 W35 / cosϕ A / --- 14.2 / 0.8 14.5 / 0.8
6 Complies with the European safety regulations
2
2. See CE declaration of conformity
7 Additional model features
7.1 Defrosting Automatic
Type of defrosting Reverse cycle
Defrosting tray included Yes (heated)
7.2 Heating water in device protected against freezing
Yes
3
3. The heat circulating pump and the heat pump controller must always be ready for operation.
7.3 Performance levels 1
7.4 Controller internal/external External