Dimplex LI MS Heat Pump User Manual


 
TECHNICAL DATA
EQUIPMENT DATA for air source heat pumps for heating purposes
1 TYPE AND COMMERCIAL DESCRIPTIONS LI11MS LI16AS
2 MODEL
2.1 Enclosure type acc to EN 60 529 for compact unit or heating element IP 21 IP 21 IP 21
2.2 Installation site Indoors Indoors
3 PERFORMANCE DATA
3.1 Operating temperature limits:
Heating water supply / return
3)
°C / °C Max. 55 / min. 18 Max. 55 / min. 18
Air °C -20 to +35 -20 to +35
3.2 Heating water temperature difference at A2 / W35 7.5 7.5
3.3 Heating capacity/coeff.of perform. at A-7 / W35
1)
kW/--- 7.6 / 2.9 9.8 / 2.6
at A2 / W35
1)
kW/--- 9.1 / 3.4 12.2 / 3.2
at A2 / W50
1)
kW/--- 9.0 / 2.5 11.5 / 2.4
at A7 / W35
1)
kW/--- 10.9 / 4.1 15.4 / 3.7
at A10 / W35
1)
kW/--- 12.0 / 4.6 16.1 / 3.8
3.4 Sound power level of unit / outside dB(A) 55 / 61 57 / 62
3.5 Heating water flow rate at internal pressure difference m
3
/h/Pa 1.0 / 3000 1.4 / 4500
3.6 Air flow rate at external static pressure difference m
3
/h/Pa 4200 / 0 5200 / 0
m
3
/h/Pa 2500 / 25 4000 / 25
3.7 Refrigerant: total charge weight Type / kg R404A / 2.5 R404A / 3.1
4 DIMENSIONS, CONNECTIONS AND WEIGHT
4.1 Equipment dimensions H x W x L mm 1360 x 750 x 850 1570 x 750 x 850
4.2 Equipment connections for heating system inches G 1” ext. thread G 1” ext. thread
4.3 Air duct inlet and outlet (min. inside dimensions) L x W mm 500 x 500 570 x 570
4.4 Weight of transport unit(s) incl. packaging kg 200 235
5 ELECTRICAL CONNECTIONS
5.1 Nominal voltage; fusing V/A 230 / 25 400 / 20
5.2 Nominal power consumption
1)
A2 W35 kW 2.65 3.81
5.3 Starting current with soft starter A 38 25
5.4 Nominal current A2 W35/cos A /--- 14.4 / 0.8 6.9 / 0.8
6 COMPLIES WITH EUROPEAN SAFETY REGULATIONS
4) 4)
7 OTHER DESIGN CHARACTERISTICS
7.1 Defrosting Automatic Automatic
Type of defrosting Cycle reversal Cycle reversal
Defrost pan available Yes (heated) Yes (heated)
7.2 Heating water inside unit protected against freezing
2)
Yes Yes
7.3 Performance settings 11
7.4 Controller internal / external External External
1)
This data characterises the size and performance capacity of the system. For economic and energy consumption reasons, additional factors such as
defrosting behaviour, bivalence point and control need to be taken into consideration. Abbreviations have the following meaning e.g. A2 / W55: heat source
temperature 2°C and heating water supply temperature 55°C.
2)
The heat circulating pump and the controller of the heat pump must be on standby at all times.
3)
See operating limits diagram.
4)
See CE Declaration of Comformity.
Subject to technical modifications