Dimplex LA 26PS Heat Pump User Manual


 
www.dimplex.de E-9
English
11
11 Device Information
1 Type and order code
LA 17PS LA 22PS LA 26PS
2Design
2.1 Degree of protection according to EN 60 529 for compact devices
and heating components
IP 24 IP 24 IP 24
2.2 Installation Location Outdoors Outdoors Outdoors
3 Performance data
3.1 Operating temperature limits:
Heating water flow/return flow
1
°C / °C
1. See operating limits diagram
Up to 65 / above 18 Up to 65 / above 18 Up to 65 / above 18
Air °C -20 to +35 -20 to +35 -20 to +35
3.2 Temperature spread of heating water at A7 / W35 9.35.09.55.09.45.0
3.3 Heat output / COP at A-7 / W35
2
kW / ---
3
2. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, other parameters, such as, in particular, the defrosting
capacity, the bivalence point and regulation, should also be taken into consideration. The specified values, e.g. A2 / W55, have the following meaning: 2 °C external air temperature
and 55 °C heating water flow temperature.
3. Operation with 1 compressors
6.7 / 2.5 6.4 / 2.4 7.7 / 2.4 7.5 / 2.3 8.7 / 2.4 8.4 / 2.2
4
4. Operation with 2 compressors
11.4 / 2.6 10.8 / 2.5 13.6 / 2.6 13.1 / 2.5 14.4 / 2.6 13.9 / 2.5
at A-7 / W45
2
kW / ---
3
6.0 / 2.2 7.0 / 2.2 7.8 / 2.3
4
10.3 / 2.2 12.5 / 2.3 13.3 / 2.3
at A2 / W35
2
kW / ---
3
8.7 / 3.2 8.3 / 3.0 10.6 / 3.1 10.5 / 3.0 11.7 / 3.1 11.5 / 3.0
4
14.5 / 3.1 14.3 / 3.0 16.7 / 3.1 16.5 / 3.0 18.8 / 3.1 18.6 / 3.0
at A7 / W35
2
kW / ---
3
10.1 / 3.6 9.6 / 3.4 12.6 / 3.8 12.0 / 3.6 13.7 / 3.6 13.3 / 3.5
4
17.3 / 3.5 16.6 / 3.4 22.0 / 3.8 21.1 / 3.5 24.0 / 3.7 22.9 / 3.5
at A7 / W45
2
kW / ---
3
9.3 / 2.9 11.3 / 3.0 12.5 / 2.9
4
16.1 / 2.9 20.5 / 3.0 21.6 / 3.0
at A10 / W35
2
kW / ---
3
11.8 / 4.1 11.4 / 4.1 13.7 / 4.2 13.5 / 4.1 15.0 / 4.1 14.7 / 4.0
4
19.6 / 3.8 19.2 / 3.8 23.4 / 4.0 23.2 / 3.9 26.2 / 4.0 25.9 / 4.0
3.4 Sound power level dB(A) 64 68 68
3.5 Sound pressure level at a distance of 10 m (air outlet side) dB(A) 37 41 41
3.6 Heating water flow with an internal pressure differential of m³/h / Pa 1.6 / 2900 3.0 / 10000 2.0 / 4500 3.5 / 13800 2.2 / 3100 3.8 / 8900
3.7 Air flow rate m³/h 5500 8000 8000
3.8 Refrigerant; total filling weight type / kg R290 / 1.8 R290 / 2.2 R290 / 2.5
4 Dimensions, connections and weight
4.1 Device dimensions H x W x L cm 157 x 155 x 85 171 x 168 x 100 171 x 168 x 100
4.2 Device connections to heating system Inch G 1 1/4'' external G 1 1/4'' external G 1 1/4'' external
4.3 Weight of the transportable unit(s) incl. packing kg 330 360 371
5 Electrical connection
5.1 Nominal voltage; fuse protection V / A 400 / 20 T 400 / 20 T 400 / 25 T
5.2 Nominal power consumption
2
A2 W35 kW
4.74 4.76 5.4 5.5 6.1 6.2
5.3 Starting current with soft starter A 23 25 30
5.4 Nominal current A2 W35 / cos ϕ A / --- 8.6 / 0.8 8.6 / 0.8 9.8 / 0.8 9.9 / 0.8 11.1 / 0.8 11.2 / 0.8
6 Complies with the European safety regulations
5
5. See CE declaration of conformity
5 5
7 Additional model features
7.1 Defrosting Automatic Automatic Automatic
Type of defrosting Hot gas Hot gas Hot gas
Defrosting tray included Yes (heated) Yes (heated) Yes (heated)
7.2 Heating water in device protected against icing
6
6. The heat circulating pump and the heat pump controller must always be ready for operation.
Yes Yes Yes
7.3 Performance levels 2 2 2
7.4 Controller internal/external External External External