Desa VGL30PRA Gas Heater User Manual


 
www.desatech.com
112882-01E
10
Minimum Noncombustible Material
Clearances
If Not Using Mantel
Note: If using a mantel, proceed to If Using
Mantel. If not using a mantel, follow the informa-
tion below.
You must have noncombustible material(s) above the
fireplace opening. Noncombustible materials (such as
slate, marble, tile, etc.) must be at least 1/2 inch thick.
With sheet metal, you must have noncombustible
material behind it. Noncombustible material must
extend at least 8" up (for all models). If noncombus
-
tible material is less than 12", you must install the
fireplace hood accessory (24" and 30" models only).
See Figure 5 for minimum clearances.
IMPORTANT: If you cannot meet these minimum
clearances, you must operate heater with chimney
flue damper open. Go to Installing Damper Clamp
Accessory for Vented Operation,
page 12.
Heat Resistant
Material
(A)
Noncombustible Requirements
Material for Safe
Distance (A) Installation
12" or more Noncombustible
material okay.
Between 8" and 12" Install fireplace hood
accessory (GA6050,
GA6052 or GA6053,
see Accessories,
page 29).
Less than 8" Noncombustible
material must be
extended to at least
8". See Between 8"
and 12", above. If
you cannot extend
material, you must
operate heater with
flue damper open.
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
INSTALLATION
Continued
If Using Mantel
You must have noncombustible material(s) above
the fireplace opening. Noncombustible materials
(such as slate, marble, tile, etc.) must be at least
1/2 inch thick. With sheet metal, you must have
noncombustible material behind it. Noncombustible
material must extend at least 8 inches up (for all
models). If noncombustible material is less than
12", you must install the fireplace hood accessory
(24" and 30" models only). Even if noncombustible
material is more than 12", you may need the hood
accessory to deflect heat away from your mantel
shelf. See Figure 5 and Figures 6 and 7 on page 11
for minimum clearances.
IMPORTANT: If you cannot meet these minimum
clearances, you must operate heater with chimney
flue damper open. Go to Installing Damper Clamp
Accessory for Vented Operation,
page 12.
MANTEL CLEARANCES
In addition to meeting noncombustible material
clearances, you must also meet required clearances
between fireplace opening and mantel shelf. If
you do not meet the clearances listed below, you
will need a hood.
Determining Minimum Mantel Clearances
If you meet minimum clearance between mantel
shelf and top of fireplace opening, a hood is not
required (see Figure 6, page 11).
Determining Minimum Mantel Clearances
When Using a Hood
If minimum clearances in Figure 6, page 11 are not
met, you must have a hood. When using a hood
there are still certain minimum mantel clearances
required. Follow minimum clearances shown in
Figure 7, page 11 when using hood.
NOTICE: Surface temperatures
of adjacent walls and mantels be-
come hot during operation. Walls
and mantels above the firebox
may become hot to the touch.
If installed properly, these tem-
peratures meet the requirements
of the national product standard.
Follow all minimum clearances
shown in this manual.