VENTING INSTALLATION
Continued
Nail Only
Outer
Perimeter
of Flashing
Storm
Collar
Flashing
Cone
Underlap
Shingles
at Bottom
Overlap
Shingles Top
and Sides Only
Figure 13 - Flashing Installation

When installing the ashing on a metal roof, it is
required that putty tape be used between the ash-
ing and the roof. The ashing must be secured to
the roof using #8 x 3/4" screws and then sealed
with roof coating to prevent leakage through the
screw holes. A roof coating must also be applied
around the perimeter of the ashing to provide a
proper seal.

Place storm collar over pipe and slide down until
it is snug against the open edge of the ashing (see
Figure 14). Apply waterproof caulk around the
perimeter of the collar to provide a proper seal.
Figure 14 - Storm Collar
Chimney
Pipe
Waterproof
Caulk
Storm
Collar
Flashing
Terminations/Spark Arrestor
The replace system must be terminated with the
listed round top or chase terminations. In any case,
refer to the installation instructions supplied with
the termination.
Secure
Termination
to Outer
Pipe with 3
Screws
RTL-10D
Level of
Flue Gas
Outlet
Stainless
Inner Flue
Pipe
Waterproof
Caulking
Storm
Collar
Flashing
Underlap
Shingles
Figure 15 - Termination
Overlap
Shingles (Top and Sides
of Flashing Base)
-
-
low the installation instructions
provided with the termination
being used.

Instructions for chase installations are included
with the chase style termination chosen. In a mul-
tiple chase installation, be sure to provide adequate
distance between terminations to prevent smoke
spillage from one termination to another. Termi-
nations be separated a minimum of 24" center to
center and stacked at a minimum vertical height
difference of 18" (see Figure 16).
Note: If a decorative shroud is to be installed,
contact the manufacturer for specications.
24" Min.
24" Min.
18"
Min.
Typ.
Figure 16 - Multiple Chase Installation