VENTING INSTALLATION
INSTRUCTIONS
Continued
Vertical Termination Configurations
Figures 21 through 24 show four different configurations for verti-
cal termination.
Venting with Two 90° Elbows
Vertical (V) Horizontal (H
1
) +
Horizontal (H
2
)
5' min. 2' max.
6' min. 4' max.
7' min. 6' max.
8' min. 8' max.
20' max. 8' max.
Figure 21 - Vertical Venting Configuration Using Two 90°
Elbows with Two Horizontal Runs (Vertical Round High Wind
Termination Shown)
Venting with One 90° Elbow
Vertical (V) Horizontal (H)
5' min. 2' max.
6' min. 4' max.
7' min. 6' max.
8' min. 8' max.
20' max. 8' max.
Figure 22 - Vertical Venting Configuration Using One 90° Elbow
(Vertical Round High Wind Termination Shown)
Note: Install restrictor
into inner collar of
fireplace as shown.
Venting with Two 90° Elbows
Vertical (V
1
) Horizontal (H)
5' min. 6' max.
6' min. 12' max.
7' min. 18' max.
8' min. 20' max.
Note: Vertical (V
1
) + Vertical (V
2
) = 40' max.
Figure 23 - Vertical Venting Configuration Using Two 90° Elbows
(Vertical Round High Wind Termination Shown)
VENTING INSTALLATION INSTRUCTIONS
Installation for Vertical Termination (Cont.)
Note: Install
restrictor into inner
collar of fireplace
as shown.
45° Elbow
Note: Install
restrictor into inner
collar of fireplace
as shown.
45° Elbow
45° Elbow