Desa CY3124N Water Heater User Manual


 
10
104340
VENT-FREE NATURAL GAS LOG HEATER
INSTALLATION
Continued
INSTALLING DAMPER
CLAMP ACCESSORY FOR
VENTED OPERATION
Note:
When used as a vented heater, appli-
ance must be installed only in a solid-fuel
burning fireplace with a working flue and
constructed of noncombustible material.
If your heater is a manually controlled model,
you may use this heater as a vented product.
There are three reasons for operating your
heater in the vented mode.
1. The fireplace does not meet the clear-
ance to combustibles requirements for
vent-free operation.
2. State or local codes do not permit vent-
free operation.
3. You prefer vented operation.
If reasons number 1 or 2 above apply to you,
you must permanently open chimney flue
damper. You must install the damper clamp
accessory (to order, see Accessories, page
27). This will insure vented operation (see
Figure 11). The damper clamp will keep
damper open. Installation instructions are
included with clamp accessory.
See chart below for minimum permanent
flue opening you must provide. Attach
damper clamp so the minimum permanent
flue opening will be maintained at all times.
Figure 11 - Attaching Damper Clamp
Damper
Damper
Clamp
Damper
Clamp
Damper
Damper
Masonry Fireplace
Chimney Minimum Permanent
Height (ft.) Flue Opening (sq. ins.)
6' to 15' 39 sq. inches
15' to 30' 29 sq. inches
Area of Various Standard
Round Flues
Diameter (ins.) Area (sq. ins.)
5" 20 sq. inches
6" 29 sq. inches
7" 39 sq. inches
8" 51 sq. inches
Manufactured Fireplace