Desa CSG3924PR Water Heater User Manual


 
www.desatech.com
110021-01M
12
Minimum
Noncombustible
Material
8"
Min.
12"
15"
18"
All minimum
distances are
in inches
20"
2
1
/2"
6"
8"
10"
12"
Distances to
Underside of
Mantel
Hood
(GA6050,
GA6052 or
GA6053)
Top of
Fireplace
Opening
Underside
of Mantel
Shelf
Mantel Shelf
INSTALLATION
Continued
Determining Minimum Mantel Clearance
when Using a Hood
If minimum clearances in Figure 6 (page 11) are
not met, you must have a hood. When using a hood
there are still certain minimum mantel clearances
required. Follow minimum clearances shown in
Figure 7 when using a hood.
NOTICE: Surface temperatures
of adjacent walls and mantels be-
come hot during operation. Walls
and mantels above the firebox
may become hot to the touch.
If installed properly, these tem-
peratures meet the requirement
of the national product standard.
Follow all minimum clearances
shown in this manual.
NOTICE: If your installation does
not meet the minimum clear-
ances shown, you must do one
of the following:
• operate the logs only with the
flue damper open
• raise the mantel to an accept-
able height
• remove the mantel
FLOOR CLEARANCES
A. If installing appliance on the floor level, you
must maintain the minimum distance of 14"
to combustibles (see Figure 8).
B. If combustible materials are less than 14" to
the fireplace, you must install appliance at
least 5" above the combustible flooring (see
Figure 9).
Hearth
5"
Min.
Combustible
Material
14"
Min.
Combustible
Material
Noncombustible Material
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
Figure 7 - Minimum Mantel Clearances When Using Hood