IMPORTANT:
Hold pressure regulator with wrench when connecting it to gas piping
and/or fittings.
* An A.G.A. design certified manual shutoff valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Purchase the optional A.G.A. design certified
manual shutoff valve from your dealer. See Accessory, page 28.
Tee Joint
Reducer
Bushing to
1/8" NPT
1/8" NPT
Plug Tap
Test
Gauge
Connection *
Pressure
Regulator
Tee
Joint
Pipe
Nipple
Cap
Sediment Trap
CHECKING
GAS
CONNECTIONS
Heater
Cabinet
3/8" NPT
Pipe Nipple
Ground Joint Union
Manual
Shutoff
Valve *
From
External
Regulator
(4" W.C. to
10.5" W.C.
Pressure)
Figure 12 - Gas Connection
3" Minimum
CONNECTING
TO GAS
SUPPLY
Continued
WARNING ICON G 001
WARNING
Test all gas piping and connections for leaks after installing or
servicing. Correct all leaks at once.
WARNING ICON G 001
WARNING
Never use an open flame to check for a leak. Apply a mixture of
liquid soap and water to all joints. Bubbles forming show a leak.
Correct all leaks at once.
PRESSURE TESTING GAS SUPPLY PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
1. Disconnect heater and its individual manual shutoff valve from gas supply
piping system. Pressures in excess of 1/2 psig will damage heater regulator.
2. Cap off open end of gas pipe where manual shutoff valve was connected.
3. Pressurize supply piping system by either using compressed air or
opening main gas valve located on or near gas meter.