6
103549
GAS RESIDENTIAL HEATERS
36"
3"
FLOOR
CEILING
Minimum
Minimum To Top Surface
Of Carpeting, Tile Or Other
Combustible Material
8"
Minimum
From
Sides Of
Heater
Right
Side
Left
Side
Figure 4 - Mounting Clearances As Viewed From Front of Heater
INSTALLING TO
WALL
NOTICE: A qualified service per-
son must install heater. Follow
all local codes.
CHECK GAS TYPE
Use only natural gas. If your gas supply is
not natural, do not install heater. Call dealer
where you bought heater for proper type
heater.
INSTALLATION ITEMS
Before installing heater, make sure you have
the items listed below.
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• manual shutoff valve *
• ground joint union
• test gauge connection * (see Figure
12, page 8)
• sediment trap
• tee joint
• pipe wrench
* An A.G.A. design-certified manual shutoff
valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Pur-
chase the optional A.G.A. design-certified
manual shutoff valve from your dealer. See
Accessory, page 12.
LOCATING HEATER
This heater is designed to be mounted on a
wall.
WARNING: Maintain the mini-
mum clearances shown in Figure
4. If you can, provide greater clear-
ances from floor, ceiling, and join-
ing wall.
WARNING: Never install the
heater
• in a bathroom
• in a recreational vehicle
• where curtains, furniture,
clothing, or other flammable
objects are less than 36 inches
from the front, top, or sides of
the heater
• as a fireplace insert
• in high traffic areas
• in windy or drafty areas
CAUTION: This heater cre-
ates warm air currents. These
currents move heat to wall sur-
faces next to heater. Installing
heater next to vinyl or cloth wall
coverings or operating heater
where impurities in the air (such
as tobacco smoke) exist, may
discolor walls.
IMPORTANT:
Vent-free heaters add mois-
ture to the air. Although this is beneficial,
installing heater in rooms without enough
ventilation air may cause mildew to form
from too much moisture. See Air for Com-
bustion and Ventilation, pages 3 through 5.
CAUTION: If you install the
heater in a home garage
• heater pilot and burner must
be at least 18 inches above
floor
• locate heater where moving
vehicle will not hit it
For convenience and efficiency, install heater
• where there is easy access for
operation, inspection, and service
• in coldest part of room