Desa CGD3924PR Water Heater User Manual


 
11
104307
OWNER’S MANUAL
INSTALLATION
Continued
CAUTION: Use only new,
black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of 1/2"
diameter or greater to allow
proper gas volume to heater. If
pipe is too small, undue loss of
pressure will occur.
Installation must include a manual shutoff
valve, union, and plugged 1/8" NPT tap.
Locate NPT tap within reach for test gauge
hook up. NPT tap must be upstream from
heater (see Figure 13).
Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged heater valves.
CAUTION: Use pipe joint seal-
ant that is resistant to liquid pe-
troleum (LP) gas.
Install sediment trap in supply line as shown
in Figure 13. Locate sediment trap where it
is within reach for cleaning. Locate sedi-
ment trap where trapped matter is not likely
to freeze. A sediment trap traps moisture
and contaminants. This keeps them from
going into heater controls. If sediment trap
is not installed or is installed wrong, heater
may not run properly.
CAUTION: Avoid damage to
regulator. Hold gas regulator with
wrench when connecting it to gas
piping and/or fittings.
* Purchase the optional A.G.A. design-certified manual shutoff valve from your dealer. See
Accessories, page 21.
** Minimum inlet pressure for purpose of input adjustment.
WARNING: Never use an open
flame to check for a leak. Apply a
mixture of liquid soap and water
to all joints. Bubbles forming show
a leak. Correct all leaks at once.
WARNING: Test all gas pip-
ing and connections for leaks
after installing or servicing. Cor-
rect all leaks at once.
CHECKING GAS
CONNECTIONS
Pressure Testing gas Supply
Piping system
Test Pressures In Excess Of 1/2 PSIG
1. Disconnect heater and its individual
manual shutoff valve from gas supply
piping system. Pressures in excess of
1/2 psig will damage heater regulator.
2. Cap off open end of gas pipe where
manual shutoff valve was connected.
3. Pressurize supply piping system by ei-
ther using compressed air or opening
propane supply tank valve.
4. Check all joints of gas supply piping
system. Apply mixture of liquid soap
and water to gas joints. Bubbles form-
ing show a leak.
5. Correct all leaks at once.
6. Re-connect heater and manual shutoff
valve to gas supply. Check re-con-
nected fittings for leaks.
Test Pressures Equal To or Less Than
1/2 PSIG
1. Close manual shutoff valve (see Fig-
ure 14, page 12).
2. Pressurize supply piping system by ei-
ther using compressed air or opening
propane supply tank valve.
3. Check all joints from propane supply
tank to manual shutoff valve (see Fig-
ure 15, page 12). Apply mixture of liq-
uid soap and water to gas joints.
Bubbles forming show a leak.
4. Correct all leaks at once.
CAUTION: Make sure exter-
nal regulator has been installed
between propane supply and
heater. See guidelines under
Con-
necting to Gas Supply
, page 10.
Figure 13 - Gas Connection
Tee Joint
Pipe
Nipple
Cap
3" Minimum
Sediment Trap
Gas
Control
From Propane
Tank (11" W.C.**
to 14" W.C.
Pressure)
A.G.A. Design-Certified Manual
Shutoff Valve With 1/8" NPT Tap*
Approved Flexible Gas Hose
(if allowed by local codes)
Continued