TECHNICAL SPECIFICATIONS
ITEM/FEATURES OFFICE PRO 60
Rating Conditions
dry bulb 95º F (35º C)
wet bulb 83º F (28.2º C)
humidity 60%
Specifications
power frequency 60Hz
line voltage single phase 208/230V
power consumption 7.1 Kw
current consumption 33 Amps
power factor 99%
starting current 140A
power wiring 6 (3-core) AWG
Cooling Unit
cooling capability 15,100 Kcal/hr
60,000 BTU/hr
cooling system direct expansion
Blower
type of fan centrifugal fan
air volume: evaporator (high speed) 1940 ft
3
/min (3296 m
3
/h)
evaporator (low speed) 1770 ft
3
/min (3007 m
3
/h)
condenser (high speed) 2830 ft
3
/min (4808 m
3
/h)
evaporator (low speed) 2650 ft
3
/min (4502 m
3
/h)
motor output: evaporator (high) 0.60 Kw
condenser (high) 1.12 Kw
Compressor
type hermetic scroll
output 4.7 Kw
refrigerant type R-22
refrigerant capacity 6.83 lbs (3.1 kg)
Safety Devices
compressor overload protector included
fan motor protector included
anti-freezing thermistor included
full drain tank switch included
automatic restart (power interruption)
included
compressor time delay program included
Dimensions & Weight
W x D x H (in) 30" x 55" x 64.4"
W x D x H (mm) 760 x 1398 x 1635
weight (lbs/kg) 625/283
Operating Conditions
inlet air (relative humidity) 106º F (41º C), 60%
65º F (18.3º C), 50%
Control Device
temperature control included
programmable timer included
two speed fan included
20