Crown Boiler KSZ125 Boiler User Manual


 
11
6) Prior to boiler installation, inspect chimney for obstructions or other defects and correct as required. Clean chimney as
necessary.
7) Vent pipe should slope upward from the boiler not less than one inch in four feet. No portion of vent pipe should run
downward or have sags. Vent pipe must be securely supported.
8) The vertical section of vent pipe coming off the boiler should be as tall as possible, while still maintaining the proper
clearance from the horizontal vent connector to combustibles and the proper pitch called for in (7) above.
9) Vent pipe should be installed above the bottom of the chimney to prevent blockage.
10) Vent pipe must be inserted flush with inside face of the chimney liner and the space between vent pipe and chimney
sealed tight. A thimble permanently cemented in place can be used to facilitate removal of chimney connector for cleaning.
11) Install the barometric draft regulator in accordance with the regulator manufacturer’s instructions.
12) Secure all joints in the vent connector system with sheet metal screws. This includes the joint between the vent connector
and the boiler collar, as well as the barometric draft regulator. Use at least three screws at each joint.
TABLE 2: MINIMUM RECOMMENDED BREECHING AND
CHIMNEY SIZE
Power (“Side Wall”) Venting - Important Note
Two problems arise when any oil-fired appliance is power vented:
1. There is sometimes an accelerated rate of soot buildup on the oil burner cad-cell, spinner etc.
2. There is a potential for severe damage to the side of the structure in the event that the boiler operates at a high smoke level.
This can happen for many reasons, some of which are out of the control of both the installer and appliance manufacturer.
Crown Boiler Company recommends the use of a chimney to vent the KSZ series boilers. If a power venter must be used, it is
the responsibility of the installer and power vent manufacturer to “engineer” the power vent system. CROWN BOILER
COMPANY WILL ASSUME NO RESPONSIBILITY FOR DAMAGE TO SIDING, ETC. FROM A POWER
VENTED OIL-FIRED BOILER. THIS APPLIES REGARDLESS OF THE CAUSE OF THE SOOTING.
10
Round I.D. (in) Rectangular I.D. (in) Height (ft)
KSZ065 6 6 8 x 8 15
KSZ075 6 6 8 x 8 15
KSZ100 6 6 8 x 8 15
KSZ090 7 7 8 x 8 15
KSZ125 7 7 8 x 8 15
KSZ150 7 7 8 x 8 15
KSZ120 8 8 8 x 8 15
KSZ175 8 8 8 x 8 15
KSZ200 8 8 8 x 8 15
Boiler
Model
Min Breeching
Dia. (inches)
Min. Recommended Chimney Size and Height