TABLE 3c: RIELLO BURNER CONFIGURATION AND SETUP DATA
XII Service and Maintenance
The following procedure should be performed on a weekly basis:
For boilers equipped with a #67 low water cut-off, blow down the low water cut-off following the instructions on the yellow
sticker adjacent to the low water cut-off. During this blow down, the low water cutoff should shut down the burner. If it does
not, the low water cut-off should be replaced immediately.
The following procedure should be performed on an annual basis:
1) Turn off electrical power and oil supply to the boiler.
2) Inspect the low water cut-off:
For Hydrolevel CG450 low water cut-offs - Remove and inspect the probe for scale and sediment buildup. Clean any
sediment or scale from the probe with a scouring pad or steel wool. Consult the Hydrolevel CG450 manual for any
additional maintenance information. Test the low water cut-off before placing the boiler back into service.
For McDonnell & Miller #67 low water cut-offs - Remove and inspect switch and float mechanism. Inspect float
bowl for mud accumulation. Clean as required. Replace the switch and float mechanism every five years or 100,000
cycles. Consult the McDonnell and Miller #67 manual for any additional maintenance information. Test the low
water cut-off before placing the boiler back into service.
KSZ065 KSZ075 KSZ100 KSZ090 KSZ125 KSZ150
KSZ120 KSZ175 KSZ200
BURNER MODEL
40F5 40F5 40F5 40F10 40F10 40F10
STANDARD
DEL DEL DEL. DEL HAGO DEL
NOZZLE
0.60/60A 0.85/60W 1.00/60A 1.25/60B
1.35/45B 1.65/45B
PUMP PRESS (psi)
150 150 150 150 150 150
TURBULATOR
02 41
1.5 2
AIR
SHUTTER SETTING
2.60 2.85 4 3
3 3.8
DRAFT OVER FIRE
(in w.c.)
MAX. SMOKE
(bacharach scale)
FLUE CO2 (%)
MIN.
11.0 11.0 11.0 11.0 11.0 11.0
MAX
12.5 12.5 12.5 12.5 12.5 12.5
-0.02 -0.02 -0.02-0.02 -0.02 -0.02
#1 #1 #1 #1 #1 #1