63
63
Pilot
light?
24 volts
between 24V
and
24V (GND) on
ign. module?
See "Intermittent
Ignition System
Troubleshooting
Chart" on page 64.
Minimum
pressure at
switch called in
Table 7 present
across switch?
* Blockage in venting system
* Vent system not installed in
accordance with installation manual
* Excessive silicone on I.D. of vent
system joints
* Blockage, condensate or leakage in
vacuum switch tubing
* Improperly sealed flue collector
* Damaged or missing fan gasket
* Defective fan
* Wind at horizontal vent terminal in
excess of 40 mph
Main
burners
light?
N
Do burner,
circulator and
fan shut down at
end of call for
heat?
END
Y
Does boiler shut
down when t'stat
wire is removed from
terminal R on
R8285?
* T'stat or zone system
calling for heat
* T'stat wires shorted
* Internal boiler wiring
problem, consult
Crown representative
Y
N
N
Y
Do burners shut
down before
gauge temp
exceeds high limit
setting +15F?
* Defective L4080D
* Sensing bulb not bottomed
out in well
N
Y
N
Y
N
Y
*Tubes reversed on
pressure switch
*Leak in tubes at pressure
switch connection
*Loose pressure switch
harness connection
Y
N
TROUBLESHOOTING CHART FOR BOILERS WITH R8285 CONTROL SYSTEM - PAGE 2 OF 2