36
Figure 32: Series 24 Minimum Piping Recommendation 2 - Water Boiler
Recommendation 2 — Use when:
• system return water is not less than 135° F for prolonged periods of time
• system flow does impact flow through the boiler(ie. zoning, mixing)
NOTES:
1. All piping is schedule 40.
2. Pipe sizes listed are based on a 20°F or 40°F differential (temperature drop).
Select one to match application.
3. When specified return piping size is less than 3”, install 3” X 12” nipple and appropriate
size bell reducer directly into boiler return tapping as shown.
4. Drain valve — ball valve preferable, gate valve acceptable alternative
(supplied by others).
- Minimum valve size per ASME code is 3/4” NPT
5. Proper boiler circulator sizing is listed in Appendix B.