Crestron electronic CLS-C6RF Indoor Furnishings User Manual


 
iLux
Integrated Lighting Systems w/infiNET
Power up and Testing Problem Solving
Troubleshooting
The following illustration shows the front panel of the
unit and the controls used during installation.
The table after this paragraph provides corrective action
for possible trouble situations. If further assistance is
required, please contact a Crestron customer service
representative.
Front Panel Controls and Indicators
CLS-C6RF/C6MRF Installation Troubleshooting
TROUBLE POSSIBLE
CAUSE(S)
CORRECTIVE ACTION
Unit is not
receiving
line power.
Verify that the unit is properly
connected to the power line and
that the circuit breaker is
closed.
Unit does not
function.
Loads are
not
connected.
Verify that the loads are
operational and that they are
connected to the iLux unit.
Loads turn on
and off, but do
not dim.
Wrong load
type
settings.
Correct load type settings. *
Lights flicker
at low levels
Incorrect
low-end
limit setting.
Change low-end limit setting. *
Verify the basic installation and wiring connections as
follows:
1. Press the Lights button to enable manual light
control, and press the right side and the left side
of each of the function buttons to increase and
decrease the lighting level of those loads. Verify
that the intended loads and corresponding LED
bargraphs respond appropriately.
* Refer to the latest version of the Crestron CLS-C6RF iLux Integrated
Lighting System w/infiNET Operations Guide (Doc. 6418), for details
on setting load types and low-end limits.
Further Inquiries
2. Press the OFF button to turn off all loads. The
loads will ramp down to off while the two-digit
display counts down to off (blank). Two seconds
after all lights have turned off, the unit’s master
air-gap relay opens making it safe to service the
lighting installations.
If you cannot locate specific information or have
questions after reviewing this guide, please take
advantage of Crestron's award winning customer service
team by calling Crestron at 1-888-CRESTRON
[1-888-273-7876].
You can also log onto the online help section of the
Crestron website (www.crestron.com/onlinehelp
) to ask
questions about Crestron products. First-time users will
need to establish a user account to fully benefit from all
available features.
Future Updates
As Crestron improves functions, adds new features, and
extends the capabilities of the CLS-C6RF and the
CLS-C6MRF, additional information may be made
available as manual updates. These updates are solely
electronic and serve as intermediary supplements prior to
the release of a complete technical documentation
revision.
Check the Crestron website periodically for manual
update availability and its relevance. Updates are
identified as an “Addendum” in the Download column.
4 iLux
Integrated Lighting Systems w/infiNET
: CLS-C6RF & CLS-C6MRF Installation Guide – DOC. 6416A