INSTALLING
Continued
Minimum Non Combustible Material Clearances
If Using Mantel
You must have non combustible material(s) above the fireplace opening. Non
combustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch
thick. With sheet metal, you must have non combustible material behind it. Non
combustible material must extend at least 8 inches up (for all models). If non
combustible material is less than 12", you must install the fireplace hood accessory
(24" and 30" models only). Even if non combustible material is more than 12", you
may need the hood accessory to deflect heat away from your mantel shelf. See
chart below and Figures 6 and 7 for minimum clearances.
IMPORTANT:
If you cannot meet these minimum clearances, you must operate
heater with chimney flue damper open. Go to Installing Damper Clamp Accessory
for Vented Operation, page 13.
Figure 6 - Minimum Mantel Clearances Without Using Hood
Non Combustible Requirements for
Material Distance (A) Safe Installation
12" or more Non combustible material OK.
Between 8" and 12" 24" or 30" Models: Install fireplace hood
acessory (GA6050 or GA6052, see
Accessories,
page 31).
18" Model: Non combustible material OK.
Less than 8" Non combustible material must be
extended to at least 8". See
Between 8"
and 12",
above. If you cannot extend
material, you must operate heater with
flue damper open.
Mantel Clearances
If you meet minimum clearance between mantel shelf and top of fireplace opening,
a hood is not required (see Figure 6).
Mantel Shelf
If above minimum clearances are not met, you must have a hood. Follow
minimum clearances shown in Figure 7 when using hood.
Continued