Chromalox CAB Electric Heater User Manual


 
DIVISION
4
SECTION
CAB
SALES
REFERENCE
SERVICE REFERENCE
161-048224-001
Chromalox
®
(Supersedes PF412-6)
Installation, Operation
and
RENEWAL PARTS INDENTIFICATION
PF412-7
© 2010 Chromalox, Inc.
Type CAB and CABB
Forced Air Duct Heaters
Model
Dimensions (In.)
(Note 1) (Note 2)
Weight
Volts Phase kW
No. No.
(Lbs.) Finstrips Ckts.
ABC
CAB-62 CAB-611
25
120, 208,
1 or 3 6 6 1 10-3/4 15-7/8 11-1/2
CABB-62 CABB-611 240 or 480
CAB-122 CAB-1211
35 208, 240 or 480 1 or 3 12 9 1 15-3/8 18-1/2 14-1/8
CABB-122 CABB-1211
CAB-152 CAB-1511
40 208, 240 or 480 1 or 3 15 9 1 15-3/8 21-5/8 17-1/4
CABB-152 CABB-1511
CAB-202 CAB-2011
55
208 or 240 3
20 12 1 20-1/8 21-5/8 17-1/4
CABB-202 CABB-2011 480 1 or 3
CAB-252 CAB-2511
65
208 or 240 3
25 12 1 20-1/8 26-1/8 21-3/4
CABB-252 CABB-2511 480 1 or 3
—— CABB-3011 75 480 3 30 18 2 29-1/2 21-5/8 17-1/4
CAB-402 CAB-4011
90
208 or 240 3
40 18 2 29-1/2 27-3/8 23
CABB-402 CABB-4011 480 1 or 3
CAB-502 CAB-5011
110
208 or 240 3
50 18 2 29-1/2 33-1/8 28-3/4
CABB-502 CABB-5011 480 1 or 3
CAB-752 CAB-7511
200
208 or 240 3
75 27 3 44-7/16 42-1/8 37-3/4
CABB-752 CABB-7511 480 1 or 3
CAB-1002 CAB-10021
220
208 or 240 3
100 27 3 44-7/16 47-1/2 43-1/8
CABB-1002 CABB-10021 480 1 or 3
1. Iron sheath strip heaters — for sheath temperatures to 750˚F.
2. Chrome steel sheath strip heaters — for sheath temperatures to 950˚F.
Sensitive Bulb of
Thermostat
2 Holes 5/16-18 Tapped,
Each Side For Mounting
A
B
C
21/32
1-9/16”
2-1/4”
3-5/8”
Type CABB
Type CAB
3/4”
4-1/4”
2-1/4”
Special Cover for Side
or Bottom Terminals
Specifications –