Chromalox 8003 Air Conditioner User Manual


 
6 Chromalox 8003 User's Manual
P9 = Alarm 1 Inhibit
Available only when P7 is different from 0.
OFF = inhibit disabled
ON = inhibit enabled
Note: The Alarm Inhibit disables the alarm action after a
setpoint change. At startup, it automatically enables the
alarm when the process temperature reaches the present
condition.
P10 = Alarm 2 Type
0 = Not provided 2 = Band alarm
1= Process alarm 3 = Deviation alarm
P11 = Alarm 2 Operative Mode
Available only when P10 is different from 0.
H = High Alarm L = Low Alarm
P12 = Alarm 2 Inhibit
Available only when P10 is different from 0
OFF = Inhibit disabled
ON = Inhibit enabled
Note: The Alarm Inhibit disables the alarm action after a
setpoint change. At startup, it automatically enables the
alarm when the process temperature reaches the present
condition.
P13 = Type of OFFSET Applied to the Measured Value
P13 = 0 = constant OFFSET (P14) all over the range
P13 different from 0 = P13 shows the application point
of the offset value set by P14 parameter.
P14 = OFFSET Value
When P13 = 0, P14 is programmable, in engineering
units, from -20 % to +20 % of the input range.
When P13 is different from 0, P14 is programmable from
-20 % to + 20 % of P13 value.
P13 = 0
Real curve
Readout
Adjusted
curve
P13
Real curve
Adjusted curve
Readout
P14
Input
P14
Input
-20% to +20%