CERTIFIED DIMENSION PRINT
OUTDOOR COIL
INDOOR COIL
INDOOR COIL ACCESS
REQ’D CLEARANCES FOR SERVICING — in. (mm)
Duct Panel ........................0
Unit Top .....................36(914.4)
Side Opposite Ducts ..............36(914.4)
Compressor Access ..............36(914.4)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L
— in. (mm)
Maximum Extension of Overhangs ......48(1219.2)
Unit Top .....................14(355.6)
Duct Side of Unit .................2(50.8)
Side Opposite Ducts ..............14(355.6)
Bottom of Unit ......................0
Flue Panel ...................36(914.4)
NEC (National Electrical Code) REQ’D CLEARANCES
— in. (mm)
Between Units, Control Box Side .......42(1066.8)
Unit and Ungrounded Surfaces,
Control Box Side ...............36(914.4)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Control Box Side . . . 42 (1066.8)
UNIT
48SS
ELECTRICAL
CHARACTERISTICS
UNIT
WEIGHT
CORNER WEIGHT
(lb/kg)
lbkgABCD
018040 208/230-1-60 272 123 81/37 62/28 76/35 53/24
024040 208/230-1-60 303 138 97/44 43/20 123/56 40/18
024060 208/230-1-60 315 143 100/45 46/21 126/57 43/20
030040 208/230-1-60 320 145 100/45 47/21 126/57 47/21
030060/080 208/230-1-60 324 147 94/43 63/29 115/52 52/24
036060/080 208/230-1-60 336 153 86/39 76/35 111/50 63/29
036100/120 208/230-1-60 348 158 89/40 79/36 114/52 66/30
042060/080 208/230-1-60 375 170 95/43 86/39 119/54 75/34
042100/120 208/230-1-60 387 176 98/45 89/40 122/55 78/35
UNIT
48SS
UNIT
HEIGHT
(in./mm)
DIMENSION
(in./mm)
CENTER OF GRAVITY
(in./mm)
EFGXYZ
018040 24.12/612.8 16
9
⁄
16
/420.7 18
15
⁄
16
/481.0 25.07/637 20.59/523 10.85/276
024040 24.12/612.8 16
9
⁄
16
/420.7 18
15
⁄
16
/481.0 27.07/688 23.35/693 10.85/276
024060 24.12/612.8 16
9
⁄
16
/420.7 18
15
⁄
16
/481.0 26.98/685 23.27/591 10.85/276
030040 24.12/612.8 16
9
⁄
16
/420.7 18
15
⁄
16
/481.0 26.71/678 23.46/596 10.85/276
030060/080 24.12/612.8 16
9
⁄
16
/420.7 18
15
⁄
16
/481.0 27.15/689 22.36/568 10.85/276
036060/080 24.12/612.8 16
9
⁄
16
/420.7 18
15
⁄
16
/481.0 27.50/698 22.48/571 10.85/276
036100/120 24.12/612.8 16
9
⁄
16
/420.7 18
15
⁄
16
/481.0 27.40/696 22.44/570 10.85/276
042060/080 28.12/714.2 20
9
⁄
16
/522.3 22
15
⁄
16
/582.6 27.01/686 22.44/570 12.65/321
042100/120 28.12/714.2 20
9
⁄
16
/522.3 22
15
⁄
16
/582.6 26.94/684 22.44/570 12.65/321
NOTE: Clearances must be maintained to prevent recircu-
lation of air from outdoor fan discharge.
3