Carrier 48SS048 Air Conditioner User Manual


 
CERTIFIED DIMENSION PRINT
INDOOR COIL
OUTDOOR COIL
INDOOR COIL ACCESS
REQ’D CLEARANCES FOR SERVICING
— in. (mm)
Duct Panel .................0
Unit Top ..............36(914.4)
Side Opposite Ducts .......36(914.4)
Compressor Access .......36(914.4)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE
MAT’L — in. (mm)
Maximum Extension of
Overhangs ...........48(1219.2)
Unit Top ..............14(355.6)
Duct Side of Unit ..........2(50.8)
Side Opposite Ducts .......14(355.6)
Bottom of Unit ...............0
Flue Panel ............36(914.4)
UNIT
48SS
ELECTRICAL
CHARACTERISTICS
UNIT
WEIGHT
CORNER WEIGHT
(lb/kg)
lb kg A B C D
048080
208/230-1-60, 208/230-3-60,
460-3-60, 575-3-60
438 199 113/51 89/40 164/75 72/33
048100/120/140
208/230-1-60, 208/230-3-60,
460-3-60, 575-3-60
450 205 116/53 92/42 165/75 77/35
060080
208/230-1-60, 208/230-3-60,
460-3-60, 575-3-60
477 217 123/56 99/45 173/79 82/37
060100/120/140
208/230-1-60, 208/230-3-60,
460-3-60, 575-3-60
489 222 126/57 102/46 173/79 88/40
UNIT
48SS
CENTER OF GRAVITY
(in./mm)
XYZ
048080 28.54/724.9 20.00/508.0 17.66/448
048100/120/140 28.22/716.8 20.05/509.3 17.66/448
060080 28.18/715.8 20.19/512.8 17.66/448
060100/120/140 27.79/705.9 20.23/513.8 17.66/448
NEC (National Electrical Code) REQ’D CLEARANCES — in. (mm)
Between Units, Control Box Side ............................42(1066.8)
Unit and Ungrounded Surfaces, Control Box Side ....................36(914.4)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Control Box Side .........................42(1066.8)
NOTE: Clearancesmust bemaintained to prevent
recirculation of air from outdoor fan discharge.
6