Carrier 42BVC Fan User Manual


 
13
1
3
2
4
4
3
1
2
1
1
2
4
3
3
4
2
RIGHT HAND UNIT
LEFT HAND UNIT
42BVC UNIT CORNER WEIGHTS (lb)
TOTAL WEIGHT UNIT CORRECTION FACTOR (lb)
Corner weights on pages 12 and 13 are for 8-row water filled coils. For a different number of rows, total unit weight
can be determined by the following procedure:
Identify the number of rows and the size of the unit.
Determine the total weight of the unit from the Corner Weight tables.
From the table below, identify the correction factor (for size of unit and number of rows) and subtract this from the
total weight.
UNITS
42BHC,BVC
4ROWS 5ROWS 6ROWS 7ROWS
Correction Factors (lb)
06 21 16 11 5
08 21 16 11 5
10 28 21 14 7
12 28 21 14 7
16 39 29 20 10
20 46 35 23 12
30 74 55 37 18
40 98 74 49 25
NOTE: Unit weights (shown in pounds) ±10% are based on the 8-row coil and 1 Hpmotor.
UNIT
42BVC
CONFIGURATION
RIGHT-HAND UNITS LEFT-HAND UNITS
TOTAL
WEIGHT
12341234
06
No Heat 52 54 51 43 54 52 43 51 200
With Heat 58 65 61 47 65 58 47 61 231
08
No Heat 53 55 51 43 55 53 43 51 202
With Heat 58 66 62 47 66 58 47 62 233
10
No Heat 63 69 61 50 69 63 50 31 243
With Heat 69 81 72 54 81 69 54 72 277
12
No Heat 64 70 62 51 70 64 51 62 247
With Heat 70 82 73 55 82 70 55 73 281
16
No Heat 74 85 72 58 85 74 58 72 289
With Heat 80 98 84 61 98 80 61 84 323
20
No Heat 90 108 86 68 108 90 68 86 351
With Heat 95 123 99 71 123 95 71 99 387
30
No Heat 110 139 106 81 139 110 81 106 436
With Heat 115 155 120 83 155 115 83 120 473
40
No Heat 131 172 125 94 172 131 94 125 522
With Heat 135 190 140 95 190 135 94 140 559