Carrier 38VYX130 Heat Pump User Manual


 
GB - 9
38VYX110/38VYX130
ENGLISH
Evacuating
Air Purge
With respect to the preservation of terrestrial environment,
adopt Vacuum pump for air purge (Evacuate air in the
connecting pipes) when installing the unit.
Do not discharge the refrigerant gas to the atmosphere to
preserve the terrestrial environment.
Use a vacuum pump to discharge the air (nitrogen, etc.)
remained in the set. If the air remains, the capacity may
decrease.
For the vacuum pump, be sure to use one with backflow
preventer so that the oil in the pump does not backflow into the
pipe of the air conditioner when the pump stops.
(If oil in the vacuum pump is put in an air conditioner including
R410A, it may cause trouble on the refrigeration cycle.)
Vacuum pump
As shown in the right figure, connect the charge hose after the
manifold valves are closed completely.
Attach the connecting port of the charge hose with a projection to
push the valve core (setting pin) to the charge port of the set.
Open handle Low fully.
Turn ON the vacuum pump.
(*1)
Loosen the flare nut of the packed valve (Gas side) a little to
check the air passes through.
(*2)
Tighten the flare nut again.
Execute vacuuming until the compound pressure gauge indicates
101kPa (76cmHg).
(*1)
Close handle Low completely.
Turn OFF the vacuum pump.
Leave the vacuum pump as it is for 1 or 2 minutes, and check the
indicator of the compound pressure gauge does not return.
Open fully the valve stem or the valve handle.
(First, at liquid side, then gas side)
Disconnect the charge hose from the charge port.
Tighten valve and caps of the charge port surely.
*1. Use the vacuum pump, vacuum pump adapters, and gauge manifold referring to the manuals attached to each tool before using them. For the vacuum
pump, check oil is filled up to the specified line of the oil gauge.
*2. While the air is purged, check again that the connecting port of charge hose, which has a projection to push the valve core, is firmly connected to the
charge port.
Compound pressure gauge
Pressure gauge
Manifold valve
Handle Hi (Keep fully closed)
Charge hose (For R410A only)
Vacuum pump adapter for counter-flow prevention
(For R410A only)
Charge hose (For R410A only)
Packed valve (Gas side)
Vacuum pump
Service port (Valve core (Setting pin))
Handle Lo
-101kPa (-76cmHg)
Valve unit
Flare nut
Valve rod
Charge port
Push in handle.
Handle
Pull out the handle and using cutting pliers, etc. turn it
counterclockwise by 90˚. (Open fully)
Close
Open Handle position
Flexible charge pipe
(only for R410A)
Vacuum pump adapter for
counter-flow prevention
(only for R410A)
Flexible charge pipe
(only for R410A)
CLOSED
completely
OPENED
fully
38VYX110 - 38VYX130