38VYX050/38VYX080
ENGLISH
Accessory and refrigerant
Table II: Accessory and Installation Parts
Refrigerant Piping
Piping kit used for the conventional refrigerant cannot be used.
Use copper pipe with 0.8 mm or more thickness for Ø 6.4, Ø 9.52,
Ø 12.7.
Outdoor unit Protective bush
Installation manual x 1 (For SM800AT only)
Drain nipple Guard material for passage
Waterproof rubber cap part (For SM800AT only)
NOTES: Caution at addition of refrigerant
(1)
When the total length of refrigerant pipe exceeds 20m, add 20g/m. The pipe total maximum length is 30 m. (Max. amount of additional refrigerant is 200g.).
Charge the refrigerant accurately. Overcharge may cause a serious trouble of compressor.
(2)
When the total length of refrigerant pipe exceeds 20m, add 40g/m. The pipe total maximum length is 50 m. (Max. amount of additional refrigerant is
1200g.). Charge the refrigerant accurately. Overcharge may cause a serious trouble of compressor.
Table III: Length of refrigerant
Length of refrigerant pipe connected
to indoor/outdoor units.
Refrigerant addition
.
20 m o shorter: for all units Do not add refrigerant at installation site
(1)
from 20 m to 30 m (38VYX 050) Add 20 g of refrigerant for every meter of pipe beyond 20 m
(2)
from 20 m to 50 m (38VYX 080) Add 40 g of refrigerant for every meter of pipe beyond 20 m
Use copper pipe with 1.0 mm or more thickness for Ø 15.87.
Flare nut and flare works are also different from those of the
conventional refrigerant.
Take out the flare nut attached to the main unit of the air
conditioner, and use it.
Cooling (2)
Maximum conditions
outdoor temperature 43°C
indoor temperature 32°C d.b.; 23°C w.b.
Minimum conditions
outdoor temperature -5°C
indoor temperature 21°C d.b.; 15°C w.b.
Heating (2)
Maximum conditions
outdoor temperature 24°C d.b.; 18°C w.b.
indoor temperature 27°C d.b.
Minimum conditions outdoor temperature 15°C d.b.
Mains power supply Nominal single-phase voltage 220÷240V ~ 50Hz
Operating voltage limits min. 198V max. 264V
Table IV: Operating limits
(1)
Notes: 1. Data referred to the outdoor unit only.
2. According to prEN14511.
d.b. - dry bulb; w.b. - wet bulb
WARNING:
During heat pump operation unit will undergo several defrost cycles to
eliminate ice that might possibly collect on the outdoor unit in very low
ambient temperatures.
In these cycles, fan speed will automatically reduce and cannot be
varied until defrost cycle is completed.