Carrier 2025 Air Cleaner User Manual


 
2
APPLICATION CONSIDERATIONS
The Infinityt Air Purifier is designed for use in the return air
duct of a forced air heating, cooling, and ventilation system.
Models GAPAAXCC1625 and GAPAAXCC2025 are
specifically designed for use in systems with a forced air gas
furnace.
Air Conditioning
The Infinityt Air Purifier should be installed in a system so
that all the return air is circulated through the air purifier. It
should be located upstream of both the furnace and the air
conditioning evaporator coil. This will help keep the furnace
and evaporator coil clean and prevent condensation from
forming within the Infinityt Air Purifier.
Humidifiers
An evaporative humidifier can be mounted upstream of the
Infinityt Air Purifier. It is best to install atomizing humidifiers
downstream of the air purifier because hard water salt deposits
and water droplets may damage air purifier. If an atomizing
humidifier must be mounted upstream of the Infinityt Air
Purifier, it should be mounted as far upstream as possible (at
least 6 ft recommended), and a standard disposable furnace
filter should be mounted between the humidifier and the air
purifier to trap hard water salt deposits and water droplets.
Transitions
If the return air duct or furnace openings do not fit the Infinityt
Air Purifier cabinet openings, gradual transitions are
recommended to reduce air turbulence and maximize efficiency.
No more than 20 degrees (about 4 in. per running ft) of
expansion should be used on each side of the transition fitting.
Turning Vanes
If the Infinityt Air Purifier is installed adjacent to a 90 degree
duct elbow, turning vanes should be added inside duct to
improve air distribution across the face of the air purifier.
Electrical Power
The Infinityt Air Purifier should only be powered when
airflow is present. The furnace control EAC terminals provide
power only when the furnace blower is operating. Infinityt Air
Purifier models GAPAAXCC1625 and GAPAAXCC2025 are
designed to be powered from the electronic air cleaner (EAC)
terminals on a furnace electronic control. If EAC terminals are
not available, an alternative airflow sensing mechanism must be
used to ensure the Infinityt Air Purifier is only powered when
airflow is present. Contact local Carrier distributor for
information on approved alternatives.
Door (x1) Cabinet (x1) Enhancement Module (x1) Safety Screen(x1)
Installation Manual
Duct GasketTape
(1 roll)
FurnaceAdapters (x2)
Return DuctAdapters:
Long (x2)/ Short(x2)
Air PurificationCartridge (x1)
(x2)
(x2)
(x1)
(x1)
(x2)
Installation Components
(in bagattached to powercord)
A06027
Fig. 2 -- Infinityt Air Purifier Components
GAPA