Alpine
16-11/16”
A
L
Low Voltage
Knockouts (24V)
Line Voltage
Knockouts (115V)
One handle on
ALP80 & 105, Two
handles on all
other models
G
(Return tapping)
F
(Gas valve inlet)
H
(Supply tapping)
3/4” FPT
relief/drain
tapping
J
(Condensate
trap drain)
M
N
O
P
D
C
E
B
Q
Model
No.
A
(in.)
B
(in.)
C
(in.)
D
(in.)
E
(in.)
F
(in.)
G
(in.)
H
(in.)
J
(in.)
L
(in.)
M
(in.)
O
(in.)
P
(in.)
Q
(in.)
ALP080 12-9/16 5-5/8 7-5/16 9-5/16 5-15/16 1/2 1 1 * 8 32-3/16 16-11/16 12-1/2 4-3/4
ALP105 14 5-13/16 7-5/16 10-3/4 5-15/16 1/2 1 1 * 8 32-3/16 16-11/16 12-1/2 4-3/4
ALP150 19-11/16 5-13/16 7-5/16 16-7/16 5-15/16 1/2 1 1 * 8 32-3/16 16-11/16 12-1/2 4-3/4
ALP210 23-15/16 5-13/16 7-5/16 17-1/8 5-15/16 1/2 1 1 * 8 32-3/16 16-11/16 12-1/2 4-3/4
ALP285 21-13/16 7-5/16 14-1/8 18 12-1/4 3/4 1-1/4 1-1/4 * 8-5/16 43-7/16 17-5/16 12-3/16 4-3/4
ALP399 28-7/8 6-3/16 13-1/16 23-3/4 15-13/16 1 1-1/2 1-1/2 * 8-5/16 43-7/16 17-5/16 12-3/16 4-3/4
*Factory provided socket end compression pipe joining clamp for 3/4” schedule 40 PVC pipe
Model No.
Input (MBH)
Output
(MBH)
Net
I=B=R
(MBH)
AFUE
(%)
Boiler Water
Volume
(gallons)
Heat Trans.
Area
(sq. ft.)
Shipping
Weight
(pounds)
Minimum Maximum
to 2k ft. 2-7k ft. 0-7k ft.
ALP080 16 27 80 73 63 95 0.6 0.6 137
ALP105 21 35 105 96 83 95 0.7 0.7 155
ALP150 30 50 150 137 119 95 1.3 1.3 182
ALP210 42 70 210 193 168 95 1.7 1.7 206
ALP285 57 57 285 263 229 95 2.4 2.4 256
ALP399 80 80 399 377* 328 94.1/94.5** 3.4 3.4 304
ALP500 – Call for product availability and additional information –
Alpine Specifications
Alpine Dimensions
NOTES: DOE Heating Capacity (ALP080 through ALP285); Gross Output (ALP399)
Maximum Working Pressure - Water: ALP080-285=30PSI; ALP399=50PSI; 80PSI optional on all models
Maximum Allowable Temperature = 210˚ F
Boilers shipped set for natural gas; field adjustment for LP (see instruction manual)
For elevations above 2000 feet, reduce ratings four percent (4%) per 1000 feet above sea level
Model
No.
Intake
Size
Vent
Size
Max
Length
ALP080 3” 3” 60’
ALP105 3” 3’ 60’
ALP150 4” 3” 60’
ALP210 4” 3” 60’
ALP285 4” 4” 60’
ALP399 4” 4” 60’
Alpine Intake / Vent Sizes
Max length in equivalent feet for each run is 60
equivalent feet of intake & 60 equivalent feet
vent length
# of 90° Elbows 2 4 6 8 10 12
Combined Intake/Vent - Feet of Pipe 110’ 100’ 90’ 80’ 70’ 60’
Maximum Vent Lengths
NOTE: Snorkels are approved for use with PVC venting.
Intake & vent lengths combined. 90° = 5 equivalent feet.
Terminals do not count towards vent feet length
** Thermal/combustion efficiency
*Gross output